Carrier 50KQA - Typical Wiring Schematics; Complete C Controller Wiring

Carrier 50KQA
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
Typical wiring schematics
2
PB
1
1
UMT
Complete
C
Cap
PBS
Transformer
Ground
CR
PB
Use copper conductors only.
NOTE 4
SEE
RVS
Not UsedNot Used
ORG
(208V)
(265V)
BRN
RED
24V
YEL
NOTE 3
SEE
ORG
230V
BLU
BLK
BM
BRN
CR
YEL
BRN
VIO
VIO
BRN
GRY
GRY
BLU
RED
RED
FP2
FP1
HP
LOC
Ground
L2
L1
Power Supply
Refer to Data Plate
See Note 2
Trans
Neutral on 265V Systems
Compressor
S
C
R
RED
BLK
8
CR
42
6
5A5
6A6
77A
A (LOW)
B (HIGH)2
BLK
BLK
RED
BLK
BRN
YEL
BLK
BLU
BLK
RED
10
1
3
1A
2A2
3A
3
1
1B
DM
YEL
YEL
ORG
BRN
GRY
YEL
YEL
RED
RED
YEL
ORG
2
RED
WV
YEL
BRN
BRN
H
C
F
CAP
PBS
WHT
(115V)
PBS
PBS
L1 (plain)
L2 (ribbed)
Ground
Optional
Cord
Connection
RED
UMT
RED
power supply connection
Refer to Disconnect
box for optional
YEL
BRN
SEE
NOTE 7NOTE 7
SEE
LOC
10
24V
12
EH1
EH2
P3
C
AL1
Microprocessor
Alarm
P1
AL2
A
Relay
SEE NOTE 6
Control Logic
CO
DC
P2
CO
FP2 Low Temp
FP1 Low Temp
CCG
W
C
R
G
O
Y
Y
R
JW2
JW1
SEE
NOTE 4
JW3
C
BR
BRG
Test Pins
Compressor
UPM
Dip Switch
Not Used
LED
Status
2
Off On
G
1
Relay
RV
FP2
FP1
HP
CC
6
9
7
8
3
5
4
2
1
MANUAL CHANGEOVER WITH COMPLETE C CONTROLLER
PUSH BUTTON SWITCH ATTRIBUTES
X = CLOSED O = OPEN
TERMINALS
1 2345678
1A 1B 2A 3A 4A 5A 6A 7A 8A
STOP
XOOOOOOOO
FAN ONLY
XOOOOXOOO
LOW COOL
OX XOOOXOO
HIGH COOL
OX XOOOOXO
LOW HEAT
XOOXXOXOO
HIGH HEAT
XOOXXOOXX
BLOWER MOTOR WIRING
UNIT SIZE POLE A POLE B
007 5 3
009 5 3
012 5 4
015 4 3
019 4 3
AL
Alarm Relay Contacts
BM
Blower Motor
BR
Blower Relay
Cap
Capacitor
CO
Condensate Overflow
CR
Compressor Relay
DM
Damper Motor
FP1
Sensor, Water Coil Freeze Protection
FP2
Sensor, Air Coil Freeze Protection
HP
High-Pressure Switch
JW1
Jumper Wire for Alarm
LOC
Loss of Charge Pressure Switch
PB
Power Terminal Block
PBS
Push Button Switch
RVS
Reversing Valve Solenoid
Trans
Transformer
UMT
Unit Mounted Thermostat
UPM
Unit Performance Monitor
WV
Water Valve
NOTES:
1. Compressor and Blower Motor thermally pro-
tected internally.
2. All wiring to the unit must comply with NEC and
local codes.
3. Transformer is wired to 115V (WHT) lead for
115/1/60 units, 265V (BRN) Lead for 265/1/60
units or 208V (RED) Lead for 208/1/60. For
230/1/60 switch RED and ORG Leads at L1
and insulate RED lead. Transformer is energy
limiting or may have circuit breaker.
4. FP1 Thermistor provides freeze protection for
WATER. When using ANTI-FREEZE solutions,
cut JW3 jumper.
5. Typical unit-mounted thermostat wiring shown.
6. 24 V Alarm Signal shown. For Dry Alarm Con-
tact, cut JW1 Jumper and Dry Contact will be
available between AL1 and AL2.
7. Transformer secondary ground via Complete C
board standoffs and screws to Control Box.
(Ground available from top two standoffs as
shown.)
>
>
>
>
>
>
LEGEND
----------
Field Line Voltage Wiring
Field Low-Voltage Wiring
Printed Circuit Trace
Optional Low Voltage
Wiring
Relay Contactor Coil
Solenoid Coil
Thermistor
Ground
Mate-N-Lock
>
>