Why won't the compressor start on my Carrier Heat Pump, but the outdoor fan is running?
- BbholmesJul 30, 2025
If the compressor of your Carrier Heat Pump won't start but the outdoor fan runs, begin by checking the wiring and connections in the compressor circuit for faults or looseness; repair or replace as necessary. The compressor motor may be burned out, seized, or have an open internal overload, requiring compressor replacement after determining the cause. Defective run/start capacitors, overloads, or start relays can also prevent the compressor from starting, so determine the cause and replace the faulty component. Lastly, check if one leg of the 3-phase power is dead; if so, replace the fuse or reset the circuit breaker and determine the underlying cause.