EasyManua.ls Logo

Carrier 50UA-UH 135 - Unit Options: Air Quality and Exhaust; Economizer with CO2 Sensor Options; Power Exhaust and Airflow Detection Options; Smoke Detector Options

Carrier 50UA-UH 135
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.00
1.50
2.00
2.50
3.00
3.50
4.00
1500
2500
3500
4500
5500
6500
7500
8500
9500
10500
-250 -200 -150 -100 -50 0
0.50
1.00
1.50
2.00
2.50
3.00
1000
2000
3000
4000
5000
6000
7000
8000
-250 -200 -150 -100 -50 0
The power exhaust performance curves are shown below:
Ưʾˀ˂Ƙʾ˃ʽÇϽÊ½ÐÀ¹ÍËÌȽʾÇÊŹƻ½
Ưʾ˅ʽƘʿʽ˂ÇϽÊ½ÐÀ¹ÍËÌȽʾÇÊŹƻ½
Return duct static pressure, Pa
Return duct static pressure, Pa
Power input, kW
ÐÀ¹ÍËÌ¹ÁÊŴÇÏƓÄƯË
Power input, kW
ÐÀ¹ÍËÌ¹ÁÊŴÇÏƓÄƯË
ʾƖ˄ƘÁÊÌÑ¾ÁÄ̽Ê¼½Ì½»ÌÁÇÆÇÈÌÁÇÆ
$IRTYlLTERDETECTIONISCONTROLLEDFROMTHETouch Pilot
control via the input from the differential pressure switch,
CHECKINGTHEPRESSUREDROPACROSSTHElLTER4HEFACTORY
setting is 250 Pa and it is adjustable. If the pressure drop
ACROSSTHElLTEREXCEEDS0ATHEREWILLBEANALARMON
the Touch Pilot control and the necessary actions will be
taken. For mechanical and electrical connections of this
OPTIONPLEASEREFERTOTHECERTIlEDDRAWINGSANDWIRING
diagrams, and to the Touch Pilot Control IOM for further
information.
ʾƖ˅ƘÍÈÈÄÑ¹ÁÊ¾ÄÇÏ¼½Ì½»ÌÁÇÆÇÈÌÁÇÆ
4HESUPPLYAIRmOWDETECTIONISCONTROLLEDBYTHETouch Pilot
control via the input from the differential pressure switch,
checking the pressure drop between the return air side and
the atmosphere. The factory setting is 20 Pa. If the pressure
drop between the return air side and the atmosphere does
not reach 20 Pa , there will be an alarm on the Touch Pilot
control and the necessary actions will be taken. For mechani-
cal and electrical connections of this option please refer to
THECERTIlEDDRAWINGSANDWIRINGDIAGRAMSANDTOTHETouch
Pilot Control IOM for further information.
ʾƖˆƘÅÇý¼½Ì½»ÌÇÊÇÈÌÁÇÆ
4HESMOKEDETECTORISFACTORYlTTEDINRETURNAIRSIDE)F
smoke is detected, there will be an alarm on the Touch Pilot
control and the necessary actions will be taken. For mecha-
nical and electrical connections of this option please refer
TOTHECERTIlEDDRAWINGSANDWIRINGDIAGRAMSANDTOTHE
Touch Pilot Control IOM for further information.
ʾƖ˂Ƙ»ÇÆÇÅÁÒ½ÊÏÁÌÀ
2
˽ÆËÇÊÇÈÌÁÇÆË
ƼÌÀ½ÊÅÇË̹ÌÁ»ÇÊ½ÆÌÀ¹ÄÈÁ»ƽ
The indoor air quality is controlled by the
Touch Pilot
control via the input from the CO
2
sensor, adjusting the
economizer. Please refer to the Touch Pilot IOM for the
control logic. The room air CO
2
sensor, together with the
connector, is in the control box. Please refer to the wiring
diagrams for the required connection and correct cable
diameter selection criteria. Sensor locations vary with
SYSTEMANDBUILDINGSPECIFICS
ʾƖ˃ƘÇϽÊ½ÐÀ¹ÍËÌÇÈÌÁÇÆ
When a large amount of fresh air is introduced into the
zone, power exhaust fans can be used to exhaust excessive
air.
The exhaust fan runs when the outside air dampers are at
least 50% open (adjustable value). It is overload protected.
4HEEXHAUSTFANISFACTORYlTTEDANDTESTEDBEFORELEAVING
the factory (see Fig. 172EFERTOTHECERTIlEDDRAWINGS
and wiring diagrams for the mechanical and electrical
connections of the power exhaust and to the Touch Pilot
Control IOM for further information.
Á¿Ɩʾ˄ƱÇϽÊ½ÐÀ¹ÍËÌÇÈÌÁÇÆ
Economizer
Dampers
Power
exhaust
ÁÊŴÇÏ
Power input
ÁÊŴÇÏ
Power input
46

Related product manuals