NOTE: The auxilial_ j reaction box (J°Box) M[ ST be relocated to
opposite side of f_/rnace casing (See Fig 12) See Electrical
Connection section fbr J-Box relocation.
CONDENSATE TRAP LOCATION
The condensate tlap must be removed from the factor-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2 or 12.
To relocate condensate trap from the blower shelf to desired
location, perform the £_llowing:
1. Remove 3 robes connected to condensate trap.
2. Remove trap fi'om blower shelf by gently pushing tabs inward
and rotating trap.
3. Install casing hole filler cap (factow-supplied in loose parts
bag) into blower shelf hole where tlap was removed.
--> (ARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injuQ'
or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate tlap is relocated to prevent combustion
products being &awn in Iiom appliances in the equipment
roonl
4. Install condensate trap into desired casing hole by inserting
robe connection stubs thro_/gh casing hole and rotating until
tabs snap into locking position
5. Fill unused condensate trap casing holes with plastic filler
caps (factolyosupplied in loose parts bag)
(ONDENSATE TRAP TUBING
NOTE: See Fig. 12 or robe routing label on main fhmace door to
check for proper connections
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
1. (ollector Box Drain Tube
a Remove _ctoryoinstalled plug from LOWER collector box
drain robe (blue and white striped label).
b. Install removed clamp and plug into UPPER collector box
&ain tube (blue label) which was previously connected to
condensate trap.
c. Connect LOWER collector box drain robe (blue and white
striped label) to condensate trap. Tube does not need to be
cut.
d. (lamp robe to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove fi_ctoryoinstalled cap and clamp from LOWER
inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer housing
&ain robe which was previously connected to condensate
tlap.
c. Install cap and clamp on UPPER inducer housing &ain
connection where molded &ain robe was removed.
d. Use inducer housing &ain extension tube (violet label and
factoryosupplied in loose parts bag) to connect LOWER
inducer housing &ain connection to condensate trap.
e. Detem_ine appropriate length, cut, and connect tube to
condensate trap.
f\ (lamp robe to prevent any condensate leakage.
3. Relief Port Tube
Refer to Pressure Switch Tubing section fbr connection
procedure.
CONDENSATE TRAP FIELD DRAIN ATTACHMENT
Refkr to Condensate Drain section fbr recommendations and
procedures.
DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX TUBE (PINK)
AUXILARY "J" BOX RELOCATED HERE
÷
CONDENSATE
TRAP
2_
DRAIN TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
Fig. 12--Horizonta{ Right Tube Configuration
12
A00214