58SB0B/58SB1B: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
31
SERVICE LABEL
A210786
Fig. 45 – Service Label
START-UP, ADJUSTMENT, AND SAFETY 
CHECK
GENERAL 
1. Maintain 115-V wiring and ground. Improper polarity will result in
rapid  flashing  control  diagnostic  light  and  Status  code  (10.1)  is
displayed. The furnace will NOT operate.
2. Make thermostat  wire  connections  at  the  24-V  terminal  block  on
the furnace control. Failure to make proper connections will result
in improper operation (see Fig. 24). 
3. Gas supply pressure to the furnace must be greater than 4.5-in. w.c.
(0.16 psig) but not exceed 14-in. w.c. (0.5 psig).
4. Check all manual-reset switches for continuity.
5. Install blower compartment door. Door must be in place to operate
furnace.
6. Replace outer door. 
Start-Up Procedures
1. Purge gas lines after all connections have been made.
2. Check gas lines for leaks.
3. To Begin Component Self-Test
a. Remove thermostat wire connected to R terminal on control to 
ensure no thermostat demands are present.
b. Temporarily depress blower door switch to power the control 
board.
c. To initiate the component test sequence, the control must be in 
(idL) mode. no thermostat demands (W, Y, G). Select 
component test (Ct) from menu select buttons to start the 
component test sequence. Once initiated the furnace control will 
perform the test sequence as shown in Table 13. Once complete, 
WARNING
!
FIRE HAZARD
Failure  to  follow  this  warning  could  result  in  personal  injury,  death
and/or property damage. 
This  furnace  is  equipped  with  manual  reset  limit  switches  in  the  gas
control area. The switches open and shut off power to the gas valve if a
flame rollout  or overheating  condition occurs  in  the  gas  control area.
DO  NOT  bypass  the  switches.  Correct  inadequate  combustion  air
supply problem before resetting the switches.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury. 
Sheet  metal  parts  may  have  sharp  edges or  burrs. Use  care  and wear
appropriate  protective  clothing,  safety  glasses  and  gloves  when
handling parts and servicing furnaces.
WARNING
!
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could cause personal injury, death and/or
property damage. 
Never  test  for  gas  leaks  with  an  open  flame.  Use  a  commercially
available soap solution made specifically for  the detection of leaks to
check all connections.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death. 
Blower  access  door  switch  opens  115-V  power  to  control.  No
component operation can occur unless switch is closed. Caution  must
be  taken.  Do  not  touch  uninsulated  electrical  components  when
manually closing this switch. for service purposes.
CAUTION
!
SHOCK HAZARD
Failure to follow this caution could result in personal injury.
Do  not  tape  or  permanently  allow  the  door  switch  to  be  bypassed.
Temporarily depress the door switch with one hand while accessing the
service  buttons  with  your  other  hand.  Do  not  touch  uninsulated
electrical components.