TYPICAL WIRING SCHEMATIC
A02186
ELECTRICAL DATA
58STA/STX
UNIT SIZE
VOLTS HERTZ
PHASE
OPERATING
VOLTAGE RANGE
MAXIMUM
UNIT AMPS
MAXIMUM
WIRE
LENGTH
FT (M)‡
MAXIMUM
FUSE OR CKT
BKR AMPS†
MINIMUM
WIRE GAGE
Maximum* Minimum*
045-08 115-60-1 127 104 5.4 49 (14.9) 15 14
045-12 115-60-1 127 104 7.0 39 (11.8) 15 14
070-08 115-60-1 127 104 5.0 52 (15.8) 15 14
070-12 115-60-1 127 104 6.8 40 (12.1) 15 14
070-16 115-60-1 127 104 9.5 29 (8.8) 15 14
090-14 115-60-1 127 104 8.2 34 (10.3) 15 14
090-16 115-60-1 127 104 10.0 28 (8.5) 15 14
090-20 115-60-1 127 104 13.6 32 (9.7) 20 12
110-12 115-60-1 127 104 8.2 34 (10.3) 15 14
110-16 115-60-1 127 104 10.1 28 (8.5) 15 14
110-22 115-60-1 127 104 14.8 30 (9.1) 20 12
135-16 115-60-1 127 104 10.2 27 (8.2) 15 14
135-22 115-60-1 127 104 14.4 30 (9.1) 20 12
155-20 115-60-1 127 104 15.0 29 (8.8) 20 12
* Permissible limits of the voltage range at w hich unit operates satisfactorily.
Time---delay type is recommended.
Length shown is as m easured 1 way along wire path between u nit and service panel for maximum 2 percent voltage drop.
58STA/STX