Carrier 61WG 020 - Application Data and Water Flow; 5.1 61 WG Operating Limits

Carrier 61WG 020
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
30WG + drycooler Minimum Maximum
Evaporator
Entering water temperature at start-up °C 7.5* 27
Leaving water temperature during operation °C 5** 20
Entering/leavingwatertemperaturedifference K 2.5 7
Condenser without hydronic kit
Entering air temperature at start-up + during
operation
°C 10-15*** 40-45****
Condenser with option 270V (kit with variable-speed pump)
Entering air temperature at start-up+ during
operation
°C -10† 40-45****
* Forenteringwatertemperaturesbelow7.5°Catstart-up,contactCarrier.
** Iftheleavingwatertemperatureisbelow5°C,afrostprotectionsolutionmust
beused.Pleaserefertooption6forevaporatorleavingwaterlow-temperature
applications(<5°C).
*** Theminimumenteringairtemperatureisbasedonthedrycoolerselection.
**** Themaximumenteringairtemperatureisbasedonthedrycoolerselection.
For applications with a low condenser entering air temperature the use of a
three-wayvalveisrecommended.Thisthre-wayvalvecanbecontrolledbythe
0-10VanalogueoutputofthePro-Dialog+control.
30WG Minimum Maximum
Evaporator
Entering water temperature at start-up °C 7.5* 27
Leaving water temperature during operation °C 5** 20
Entering/leavingwatertemperaturedifference K 2.5 7
Condenser
Entering water temperature at start-up °C 15*** 55****
Leaving water temperature during operation °C 20 60
Entering/leavingwatertemperaturedifference K 2.5 18
* Forenteringwatertemperaturesbelow7.5°Catstart-up,contactCarrier.
** Iftheleavingwatertemperatureisbelow5°C,afrostprotectionsolutionmust
beused.Pleaserefertooption6forevaporatorleavingwaterlow-temperature
applications(<5°C).
*** Forapplicationswithacondenserenteringtemperaturebelow15°Ctheuseof
athree-wayvalveisrecommended.Thisthree-wayvalvecanbecontrolledby
the0-10VanalogueoutputofthePro-Dialog+control.
**** Forawaterowratethatcorrespondstoamaximumwater-sidetemperature
differenceof5K.
30WG + option 6 Minimum Maximum
Evaporator
Entering water temperature at start-up °C -9.5* 27
Leaving water temperature during operation °C -12* 20
Entering/leavingwatertemperaturedifference K 2.5 3
Condenser
Entering water temperature at start-up °C 15** 55***
Leaving water temperature during operation °C 20 60
Entering/leavingwatertemperaturedifference K 2.5 18
Note:Donotexceedthemaximumoperatingtemperature.
* Afrostprotectionsolutionmustbeused.
** Forapplicationswithacondenserenteringtemperaturebelow15°Ctheuseof
athree-wayvalveisrecommended.Thisthree-wayvalvecanbecontrolledby
the0-10VanalogueoutputofthePro-Dialog+control.
*** Forawaterowratethatcorrespondstoamaximumwater-sidetemperature
differenceof5K.
5.2 - Operating range 61WG
Condenserleavingwatertemperature,°C
Evaporatorleavingwatertemperature,°C
Evaporatorleavingwatertemperature,°C
Condenserleavingwatertemperature,°C
15
20
25
30
35
40
45
50
55
60
65
-8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20
Standard
Option 272
61WG standard unit
61WGunitwithoption272(brinetowater)
15
20
25
30
35
40
45
50
55
60
65
-14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20
Standard
Option 6
5 - APPLICATION DATA
5.1 - Operating limits 61WG
61WG Minimum Maximum
Evaporator
Entering water temperature at start-up °C 7.5* 27
Leaving water temperature during operation °C 5** 20
Entering/leavingwatertemperaturedifference K 2.5 7
Condenser
Entering water temperature at start-up °C 15*** 60****
Leaving water temperature during operation °C 20 65
Entering/leavingwatertemperaturedifference K 2.5 18
* Forenteringwatertemperaturesbelow7.5°Catstart-up,contactCarrier.
** Iftheleavingwatertemperatureisbelow5°C,afrostprotectionsolutionmust
beused.Pleaserefertooption272forevaporatorleavingwaterlow-temperature
applications(<5°C).
*** Forapplicationswithacondenserenteringtemperaturebelow15°Ctheuseof
athree-wayvalveisrecommended.Thisthree-wayvalvecanbecontrolledby
the0-10VanalogueoutputofthePro-Dialog+control.
**** Forawaterowratethatcorrespondstoamaximumwater-sidetemperature
differenceof5K.
61WG + option 272 (geothermal application) Minimum Maximum
Evaporator
Entering water temperature at start-up °C -2.5* 25
Leaving water temperature during operation °C -5* 20
Entering/leavingwatertemperaturedifference K 2.5 5
Condenser
Entering water temperature at start-up °C 15** 60***
Leaving water temperature during operation °C 20 65
Entering/leavingwatertemperaturedifference K 2.5 18
* Afrostprotectionsolutionmustbeused.
** Forapplicationswithacondenserenteringtemperaturebelow15°Ctheuseof
athree-wayvalveisrecommended.Thisthree-wayvalvecanbecontrolledby
the0-10VanalogueoutputofthePro-Dialog+control.
*** Forawaterowratethatcorrespondstoamaximumwater-sidetemperature
differenceof5K.
5.4 - Operating range 30WG
30WGstandardunit
30WGunitwithoption6(brine)
5.3 - Operating limits 30WG