EasyManua.ls Logo

Carrier AquaEdge 23XRV - Cooler; Control Center; Condenser; Motor-Compressor

Carrier AquaEdge 23XRV
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
Cooler — The cooler (also known as the evaporator) is
maintained at low temperature/pressure so that evaporating
refrigerant can remove heat from the liquid flowing through its
internal tubes.
Condenser — This vessel is located underneath the
compressor. The condenser operates at a higher temperature/
pressure than the cooler and has liquid flowing through its
internal tubes to remove heat from the refrigerant.
Motor-Compressor — The motor-compressor main-
tains system temperature/pressure differences and moves the
heat carrying refrigerant from the cooler to the condenser. See
Fig. 8.
Muffler — The muffler provides acoustical attenuation. A
check valve just downstream of the muffler prevents reverse
compressor rotation during shutdown.
Control Center — The control center is the user inter-
face for controlling the chiller and regulating the chiller’s
capacity to maintain the proper chilled liquid temperature. See
Fig. 9. The control center:
registers cooler, condenser, and lubricating system pressures
shows chiller operating condition and alarm shutdown
conditions
records the total chiller operating hours, starts, and the
number of hours the chiller has been currently running
sequences chiller start, stop, and recycle under microproces-
sor control
provides access to other Carrier Comfort Network
®
devices
provides machine protection
Storage Vessel (Optional) — Two sizes of storage
vessels are available. The vessels have double relief valves,
a magnetically coupled dial-type refrigerant level gage, a
1-in. FPT drain valve, and a
1
/
2
-in. male flare vapor connection
for the pumpout unit. A 30-in.-0-400 psi (–101-0-2750 kPa)
gage is also supplied with each unit.
NOTE: If a storage vessel is not used at the jobsite, factory-
installed optional isolation valves may be used to isolate the
chiller charge in either the cooler or condenser. An optional
pumpout compressor system is used to transfer refrigerant
from vessel to vessel.
DISCHARGE
COMPRESSOR LUBRICATION BLOCK
MOTOR TERMINAL
ACCESS COVER
MOTOR COOLING
DRAIN
MOTOR TERMINALS ECONOMIZER
PORT
MOTOR
COOLING
INLET
FLANGE
Fig. 8 — Compressor (Typical, R Compressor Shown)
a23-1619

Table of Contents

Other manuals for Carrier AquaEdge 23XRV

Related product manuals