APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Table G — Network Points List
LEGEND
POINT DESCRIPTION
CCN
POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Active Delta T DT_A_ R psi N/A 0 to 200 AV:4 dt_a_1
Active Demand Limit DEM_LIM R/W % N/A 40 to 100 AV:5 dem_lim_1
Actual VFD Speed VFD_ACT R % N/A 0 to 110 AV:6 vfd_act_1
Auto Chilled Liq Reset AUTO_RES R mA N/A 4 to 20 AV:7 auto_res_1
Auto Demand Limit Input AUTO_DEM R mA N/A 4 to 20 AV:8 auto_dem_1
Base Demand Limit DLM R/W % N/A 40 to 100 AV:9 dlm_1
Calc Evap Sat Temp ERT R °F N/A -40 to 245 AV:10 ert_1
Chill Liq Pulldown/Min CHL_PULL R/W ^F N/A -20 to 20 AV:13 chl_pull_1
Chilled Liquid Temp CHL_TMP R °F N/A -40 to 245 AV:11 chl_tmp_1
Chilled Water Temp CHWTEMP R °F N/A 0.0 to 99.9 AV:12 chwtemp_1
Chiller Start/Stop CHIL_S_S R/W N/A STOP/START BV:5 chil_s_s_1
Comp Discharge Alert CD_ALERT R °F 140 125 to 160 AV:14 cd_alert_1
Comp Discharge Temp CMPD R °F N/A -40 to 245 AV:15 cmpd_1
Comp Motor Frequency VFD_FREQ R Hz N/A 0 to 10000 AV:49 vfd_freq_1
Comp Motor RPM CPR_RPM R rpm N/A 0 to 300000 AV:50 cpr_rpm_1
Condenser Liquid Pump CDP N/A OFF/ON BV:4 cdp_1
Condenser Pressure CRP R psi N/A -6.7 to 420 AV:16 crp_1
Condenser Refrig Temp CRT R °F N/A -40 to 245 AV:17 crt_1
Control Mode MODE R N/A
0=Off, 1=Local ,
2=CCN, 3=Reset
AV:51 mode_1
Control Point LCW_STPT R/W °F N/A 10 to 65 AV:18 lcw_stpt_1
Current CHW Setpoint CHWSTPT R °F N/A 0.0 to 99.9 AV:19 chwstpt_1
Demand Level 1 R % N/A 0 to 100 AV:1 dmv_lvl_1_perct_1
Demand Level 2 R % N/A 0 to 100 AV:2 dmv_lvl_2_perct_1
Demand Level 3 R % N/A 0 to 100 AV:3 dmv_lvl_3_perct_1
Element Communications Alarm RN/A
Comm Normal
Comm Lost
BV:15 comm_lost_alm_1
Element Comm Status R N/A No Comm/Normal BV:2999 element_stat_1
Entering Chilled Liquid ECL R °F N/A -40 to 245 AV:20 ecl_1
Entering Cond Liquid ECDL R °F N/A -40 to 245 AV:21 ecdl_1
Evap Refrig Liquid Temp EST R °F N/A -40 to 245 AV:23 est_1
Evap Refrig Trippoint ERT_TRIP R °F 33 10 to 40.0 AV:24 ert_trip_1
Evaporator Pressure ERP R psi N/A -6.7 to 420 AV:22 erp_1
Ground Fault Current GF_AMPS R A N/A 0 to 999 AV:25 gf_amps_1
Head Pressure Reference HPR R % N/A 0 to 100 AV:52 hpr_1
Leaving Chilled Liquid -
Prime Variable
LCL R °F N/A -40 to 245 AV:26 lcl_1
Leaving Cond Liquid LCDL R °F N/A -40 to 245 AV:27 lcdl_1
Local Schedule R N/A ON/OFF BV:1 schedule_1
Occupied? OCC R NO/YES BV:6 occ_1
Oil Heater Relay 1 OILHEAT1 R N/A OFF/ON BV:7 oilheat1_1
Oil Heater Relay 2 OILHEAT2 R N/A OFF/ON BV:11 oilheat2_1
Oil Pump Relay OILR R N/A OFF/ON BV:8 oilr_1
Oil Pressure Delta P OILPD R psi N/A -6.7 to 420 AV:28 oilpd_1
Oil Sump Temp OILT R °F N/A -40 to 245 AV:29 oilt_1
Percent Line Current LNAMPS_P R % N/A 0.0 to 9999 AV:30 lnamps_p_1
Percent Line Kilowatts LINEKW_P R % N/A 0.0 to 9999 AV:31 linekw_p_1
CHW Chilled Water
R—Read
VFD Variable Frequency Drive
W—Write
516