Table 3 — ICVC Display Data (cont)
EXAMPLE 8 — POWER DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation.
MENU
STATUS
POWER
SELECT
DESCRIPTION STATUS UNITS POINT
Percent Line Current 0 to 999 % LNAMPS_P
Average Line Current 0 to 99999 AMPS LNAMPS_A
Percent Line Voltage 0 to 999 % LNVOLT_P
Average Line Voltage 0 to 99999 VOLTS LNVOLT_A
Line Power Factor 0.0 to 2.0 LINE_PF
Line Kilowatts 0 to 99999 KW LINE_KW
Percent Line Kilowatts 0 to 99999 % LINEKW_P
Percent Load Current 0 to 99999 % LDAMPS_P
Average Load Current 0 to 99999 AMPS LDAMPS_A
Motor Power Factor 0.0 to 2.0 MOTOR_PF
Motor Kilowatts 0 to 99999 KW MOTOR_KW
Percent Motor Kilowatts 0 to 99999 % MOTORKWP
Motor Kilowatt-Hours 0 to 99999 KWH MOTORKWH
Demand Kilowatts 0 to 99999 KW DEM_KW
Line Current Phase 1 (R) 0 to 99999 AMPS LN_AMPS1
Line Current Phase 2 (S) 0 to 99999 AMPS LN_AMPS2
Line Current Phase 3 (T) 0 to 99999 AMPS LN_AMPS3
Load Current Phase 1 (U) 0 to 99999 AMPS LD_AMPS1
Load Current Phase 2 (V) 0 to 99999 AMPS LD_AMPS2
Load Current Phase 3 (W) 0 to 99999 AMPS LD_AMPS3
Line Voltage Phase 1 (RS) 0 to 99999 VOLTS LN_VOLT1
Line Voltage Phase 2 (ST) 0 to 99999 VOLTS LN_VOLT2
Line Voltage Phase 3 (TR) 0 to 99999 VOLTS LN_VOLT3
Ground Fault Current 0 to 999 AMPS GF_AMPS
Line Frequency 0 to 99 Hz LINEFREQ
Rectifier Overload 0 to 100 % RECT_OV
Inverter Overload 0 to 100 % INV_OV
Motor Overload 0 to 100 % MOTOR_OV
Line Current Imbalance 0 to 100 % LN_IMB_I
Motor Current Imbalance 0 to 100 % MT_IMB_I
Line Voltage Imbalance 0 to 100 % LN_IMB_V
Line Active Current 0 to 99999 AMPS AMPS_ACT
Line Reactive Current 0 to 99999 AMPS AMPS_RE
Line Active Voltage 0 to 99999 VOLTS VOLT_ACT
Line Reactive Voltage 0 to 99999 VOLTS VOLT_RE
DC Bus Voltage Reference 0 to 99999 VOLTS BUS_REF
DC Bus Voltage 0 to 99999 VOLTS BUS_VOLT
Flux Current 0 to 99999 AMPS FLUXAMPS
Torque Current 0 to 99999 AMPS TORQAMPS
Inverter Temperature 0 to 300 °F (°C) INV_TEMP
Rectifier Temperature 0 to 300 °F (°C) REC_TEMP
VFD Dewpoint 0.0 to 300.0 °F (°C) VFDDEWPT
VFD Enclosure Temperature 0 to 300 °F (°C) VFD_ENCL
VFD Cold Plate Temperature 0 to 300 °F (°C) CP_TEMP
Humidity Sensor Input 0.0 to 5.0 VOLTS HUMID_SR
Relative Humidity 0 to 100 % HUMIDITY
VFD Coolant Flow 0 to 100 % VFD_FOUT
Actual VFD Speed 0 to 100 % VFD_ACT
Comp Motor RPM 0 to 300000 rpm CPR_RPM
Comp Motor Frequency 0 to 10000 Hz VFD_FREQ
Comp Maximum Speed 0 to 101 Hz MAXSPEED
Comp Minimum Speed 0 to 100 % MINSPEED