RATED DRY WEIGHT AND REFRIGERANT CAPACITY
ENGLISH (lb)
SI (kg)
TANK
SIZE
TANK OD
(in.)
DRY
WEIGHT*
(lb)
R-134A MAXIMUM REFRIGERANT CAPACITY (lb)
ANSI/ASHRAE 15 UL 1963
0428 24.00 2334 1860 1716
0452 27.25 3414 3563 3286
TANK
SIZE
TANK OD
(mm)
DRY
WEIGHT*
(kg)
R-134A MAXIMUM REFRIGERANT CAPACITY (kg)
ANSI/ASHRAE 15 UL 1963
0428 610 1059 844 778
0452 692 1549 1616 1491
LEGEND
*The above dry weight includes the pumpout condensing unit weight of 164 lb (75 kg).
ANSI — American National Standard Institute
ASHRAE — American Society of Heating, Refrigeration,
and Air-Conditioning Engineers
OD — Outside Diameter
UL — Underwriters Laboratories
Fig. 41 — Optional Pumpout System Piping Schematic with Storage Tank — Configured to Push
Liquid into Storage Tank (Unit with R Compressor Shown)
a23-1634