Installation Instructions
25HBB, 25HBC, 25HCD
Comfortt Seri es He at Pumps
with Puronr Refrigerant
1–1/2 To 5 Nominal Tons
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory–authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety–alert symbol
!
!
.
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words; DANGER, WARNING, and
CAUTION. These words are used with the safety–alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
!
WARNING
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate
for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding un-
necessary turns and bends.
4. Leave some slack between structure and unit to absorb vi-
bration.
5. When passing refrigerant tubes through the wall, seal open-
ing with RTV or other pliable silicon–based caulk (see Fig.
1).
6. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with
tubing (see Fig. 1).
8. Ensure that tubing insulation is pliable and completely sur-
rounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation (see Fig. 1).
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
INSULATION
SUCTION TUBE
LIQUID TUBE
OUTDOOR WALL INDOOR WALL
LIQUID TUBE
SUCTION TUBE
INSULATION
CAULK
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
JOIST
1” (25.4 mm)
MIN
THROUGH THE WALL
SUSPENSION
A07588
Fig. 1 -- Connecting Tubing Installation
When outdoor unit is connected to factory–approved indoor unit,
outdoor unit contains system refrigerant charge for operation with
AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
field–supplied or factory accessory tubing. For proper unit
operation, check refrigerant charge using charging information
located on control box cover and/or in the Check Charge section of
this instruction.
IMPORTANT: Maximum liquid–line size is 3/8–in. OD for all
residential applications including long line.
IMPORTANT: Always install the factory–supplied liquid–line
filter drier. Obtain replacement filter driers from your distributor or
branch.
Question and Answer IconNeed help?

Do you have a question about the Carrier Comfort 25HCD series and is the answer not in the manual?

Carrier Comfort 25HCD series Specifications

General IconGeneral
TypeHeat Pump
SEERUp to 16
RefrigerantR-410A
Voltage208/230
Phase1
Heating Capacity (BTU/h)18, 000 - 60, 000
Sound Level (dBA)72

Summary

Installation Instructions

Safety Considerations

Essential safety precautions and warnings to prevent injury or death during installation.

Installation Recommendations

Guidelines for proper unit placement and tubing installation to minimize operational noise.

Piping Connections

Refrigerant Tubing & Sweat Connections

Instructions for connecting refrigerant lines and making brazed joints for system integrity.

Electrical Connections

Route Ground and Power Wires

Guidance on routing power and ground wires safely within the unit's control box.

Connect Ground & Power Wires

Steps for securely connecting ground and power wiring to the unit's contactor.

Connect Control Wiring

Details for routing and connecting 24v control wires for thermostat and system operation.

System Start-Up

Final Wiring Check

Final checks of all wiring and tubing security before energizing the system.

Compressor Crankcase Heater

Procedure for powering the compressor crankcase heater prior to system startup.

Electrical Accessories Installation

Guidance for installing any optional electrical accessories.

Sequence of Operation

Explanation of system operation modes: cooling, heating, and defrost cycles.

Refrigerant Charge Check

Cooling Mode TXV Charge

Procedure for checking system refrigerant charge using the subcooling method for TXV systems.

Indoor Piston Charge

Procedure for checking system refrigerant charge using the superheat method for piston systems.

Heating Check Chart Procedure

Method to verify correct system refrigerant charge during heating operation.

Final Installation Checks

Pre-Operation System Verification

Crucial final checks to ensure proper installation before system handover to the owner.

Care and Maintenance

Periodic Maintenance Importance

Emphasizing periodic maintenance for sustained performance and equipment longevity.