SETPOINTS
(cont)
ERV OAT SP 32°F (0°C)
0°F to 50°F
(–18°C to 10°C);
increment by 1°
ENERGY RECOVERY VENTILATION UNIT OUTDOOR AIR
TEMPERATURE SETPOINT
Only displayed when AUX1 O = ERV
EXH1 SET 50% 0 to 100%
Exhaust fan set point for single speed units. Based on OA Damper position
to activate power exhaust.
EXH1 L SET 65% 0 to 100%
EXHAUST FAN 1 SETPOINT AT LOW SPEED
On 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA
damper position to activate power exhaust.
EXH1 M SET 60% 0 to 100%
EXHAUST POINT 1 SETPOINT AT MEDIUM SPEED
Only displays if unit is set for 3 speed with 1 heat and 2 cool. Based on
economizer OA damper position to activate power exhaust.
EXH2 H SET 50% 0 to 100%
EXHAUST FAN 1 SETPOINT AT HIGH SPEED
On 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA
damper position to activate power exhaust.
EXH2 L SET 80% 0 to 100%
EXHAUST FAN 2 SETPOINT AT LOW SPEED
On 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA
damper position to activate power exhaust.
EXH2 M SET 77% 0 to 100%
EXHAUST FAN 2 SETPOINT AT MEDIUM SPEED
Only displays if unit is set for 3 speed with 1 heat and 2 cool. Based on
economizer OA damper position to activate power exhaust.
EXH2 H SET 75% 0 to 100%
EXHAUST FAN 2 SETPOINT AT HIGH SPEED
On 2 speed or 3 speed with 1 heat and 2 cool. Based on economizer OA
damper position to activate power exhaust.
SYSTEM
SETUP
INSTALL 01/01/10
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG °F °F or °C Sets economizer controller in degrees Fahrenheit or Celsius
EQUIPMENT CONV
Conventional or
HP
Always set to CONV even for heat pump
AUX2 I W
W required for
2-speed mode
Always set to W
FAN TYPE 2 speed 1 speed/2 speed
Sets the economizer controller to the number of unit fan speeds.
Fan Type options:
1 Speed units
2 speed units
*2 speed units: 1 for heat and 1 for cool
*3 speed units: 1 for heat and 2 for cool
* These Fan Type (speed) settings are for future use only. Do not use for 3 speed LC units.
FAN CFM 5000cfm
100 to 15000 cfm;
increment by 100
UNIT DESIGN AIRFLOW (CFM)
Enter ONLY if using DCVCAL ENA = AUTO
AUX OUT NONE
NONE
ERV
EXH2
SYS
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilation
• EXH2 = second damper position relay closure for second exhaust fan
• SYS = use output as an alarm signal
OCC INPUT
INPUT or
ALWAYS
Always set to INPUT
ADVANCED
SETUP
MA LO SET 45°F (7°C)
35°F to 55°F
(2°C to 12°C);
incremented by 1°
MIXED AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and alarm if
temperature falls below setup value).
FREEZE POS CLO CLO or MIN
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active
CLO = closed
MIN = MIN POS or VENTMIN
CO2 ZERO 0ppm
0 to 500 ppm;
Increment by 10
CO
2
ppm level to match CO
2
sensor start level.
CO2 SPAN 2000ppm
1000 to 3000 ppm;
Increment by 10
CO
2
ppm span to match CO
2
sensor.
STG3 DLY 2.0h
0 min, 5 min, 15
min, then 15 min
intervals. Up to 4 h
or OFF
COOLING STAGE 3 DELAY
Delay after stage 2 for cool has been active. Turns on 2nd stage of cooling
when economizer is 1st stage and mechanical cooling is 2nd. Allows three
stages of cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling
SD DMPR POS CLO CLO or OPN
Function NOT AVAILABLE with 2-speed mode
Indicates shutdown signal from space thermostat or unitary controller. When
controller receives 24 vac input on the SD terminal in conventional mode, the
OA damper will open if programmed for OPN and OA damper will close if
programmed for CLO. All other controls, e.g., fans, etc. will shut off.
DCVCAL ENA MAN
MAN (manual)
AUTO
Turns on the DCV automatic control of the dampers. Resets ventilation
based on the RA, OA, and MA sensor conditions. Requires all 3 RA, OA, and
MA sensors.
For single speed units only.