15
(Discharge Air Temperature), depending on how its three
position DIP switch is set.
Use Fig. 10 and Table 8 to locate the wiring terminals for
each Enthalpy Control sensor.
Use Fig. 10 and Table 9 to set the DIP switches for the
desired use (location) of the sensor.
2-1/64 (55)
51/64 (21)
4-1/4 (108)
2-3/4 (70)
NOTE: Dimensions in ( ) are in mm
C12036
Fig. 10 -- Enthalpy Control Sensor, Dimensions and
DIP Switch Location
Table 8 – Enthalpy Control Sensor Wiring Terminations
a
Ter m ina l
Type Description
Nbr Label
1 S --- B U S S --- B U S
S --- B u s C o m m u n i c a t i o n s
(Enthalpy C ontrol Sensor Bus)
2 S --- B U S S --- B U S
S --- B u s C o m m u n i c a t i o n s
(Enthalpy C ontrol Sensor Bus)
a Terminals are polarity insensitive.
Table 9 – Enthalpy Control Sensor DIP Switch Settings
Use
DIP Switch Positions for Switches 1, 2, & 3
1 2 3
DA
a
OFF ON OFF
RA
b
ON OFF OFF
OA
c
OFF OFF OFF
aDA=DischargeAir
bRA=ReturnAir
c OA = Outside Air
When a S--bus sensor is connected to an existing network,
it will take 60 minutes for the network to recognize and
auto--configure itself to use the new sensor. During the 60
minute setup period, no alarms for sensor failures (except
SAT) will be issued and no economizing function will be
available.
LLECON--02SI