22
CONTROL SET POINT AND CONFIGURATION LOG
Project Name/Location:
Model Number:
Serial Number:
Date:
Technician
Menu Tables:
1. SYSTEM SETUP
2. ADVANCED SETUP
3. SETPOINTS
Menu 1: System Setup
Parameter
Project
Value
Parameter
Default
Value
Parameter
Range and Increment
Notes
INSTALL 01/01/10 Display order = MM/DD/YY
Setting order = DD, MM, then YY
UNITS DEG _F _F or _C Sets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENT CONV CONV required for
2 --- s p e e d m o d e
CONV = conventi onal ;
HP O/B = Enable Heat Pump mode; not available with 2---speed
SeeMenuNote4(onpage8)
AUX2 I W Wrequiredfor
2 --- s p e e d m o d e
W = Informs controller that system is in heating mode.
SD = Enables configurat i on of shutdown (not availa bl e on 2--- spe ed)
SeeMenuNote4(onpage8)
FAN TYPE 2speed 2speed required Sets the economizer controller for operation of 1 speed or 2 speed
indoor fan system.
SeeMenuNote4(onpage8)
FAN CFM 5000cfm 100 to 15000 cfm; UNIT DESIGN AIRFLOW (CFM)
Enter ONLY if using DCVCAL ENA = AUTO
The value is found in the Project Submit t al document s for the speci fic
RTU .
AUX OUT NONE NONE
ERV
EXH2
SYS
Select OUTPUT for AUX1 O relay
NONE = not configur ed (output is not used)
ERV = Energy Recovery V entilator
EXH2 = second damper position relay closure for second exhaust fan
SYS = use output as an alarm signal
OCC INPUT INPUT or ALWAYS OCCUPIED MODE BY EXTERNAL SIGNAL
When using a set back therm os ta t with occ upancy out (24 Vac) , the
24---Vac is input to the OCC terminal. RTU control circuit provides
24--- V ac to OCC through OCCUPIED terminals on Central Terminal
Boar d. (se e Menu Note 2 (on page 8)
FACTORY DEFAULT NO NO or YES Resets all set points to factory defaults when set to YES. LCD will
brie fl y flas h YES and change to NO but al l paramet e rs wil l change to
the factory default values.
RECHECK AUX2 I and FAN TYPE for required 2---speed values.
LLECON--02SI