Menu 2: Advanced Setup
Parameter
Project
Value
Parameter
Default
Value
Parameter
Range and Increment
Notes
MA LO SET 45_F(7_C) 35 to 55_F;
(2 to 13_C)
incremented by 1_
SUPPL Y AIR TEMPERATRUE LOW LIMIT
Temperature to achieve F reeze Protecti on (clos e damper and alarm if
temperature at SAT location falls below setup value)
FREEZE POS CLO CLO or MIN FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active
CL O =c lo sed
MIN = MIN POS or VENTMAX
CO2 ZERO 0ppm 0 to 500 ppm:
Increment by 10
CO
2
ppm level to match CO2 Sensor start level.
CO2 SPAN 2000ppm 1000 to 3000 ppm;
Increment by 50
CO
2
ppm span to match CO2 sensor.
STG3 DLY 2.0h 0 min, 5 min, 15 min,
then 15 min intervals.
Up to 4 h
or OFF
COOLIN G ST A G E 3 DEL AY
Delay after stage 2 for cool has been active. T urns on 2nd stage of
coo l ing when econo m ize r is 1st stage and mechani cal cool ing is 2nd
SD DMPR POS CLO CLO or OPN F unction NOT AV AI LABLE with 2---speed mode
DCVCAL ENA MAN MAN (manual) Turns on the DCV autom ati c control of the dampers . Resets ventilat i on
MATTCAL 0.0 1.0_F
(or _C)
+/ --- 2 . 5 _F
( + / --- 1 . 4 _C)
SUPPL Y AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration supply air
tem peratur e (SA T) senso r
OA T CAL 2.0 3.0_F
(or _C)
+/ --- 2 . 5 _F
( + / --- 1 . 4 _C)
OUTSIDE AIR TEMPERATURE CALIBRATION
All ows for the operator to adjust for an out of calibrati on outsi de air
tem peratur e (OAT) senso r
OA H CAL 0% RH + / --- 1 0 % R H OUTSIDE AIR HUMIDITY CALIBRATION
All ows for the operator to adjust for an out of calibrati on of outsi de air
enthalpy sensor
RA T CAL 4.0 5.0_F
(or _C)
+/ --- 2 . 5 _F
( + / --- 1 . 4 _C)
RETURN AIR TEMPERATURE CALIBRA TION
Allows for the operator to adjust for an out of calibration return air
temperature (RA) sensor
RA H CAL 0% RH + / --- 1 0 % R H RETURN AIR HUMIDITY CALIBRATION
Allows for the operator to adjust for an out of calibration return air
enthalpy sensor
DA T CAL 0.0 1.0_F
(or _C)
+/ --- 2 . 5 _F
( + / --- 1 . 4 _C)
DISCHARGEAIRTEMPERATURECALIBRATION
All ows for the operator to adjust for an out of cali bratio n disc harge air
tem peratur e (DA T) senso r
2SP FAN DELAY 5 Minutes 0to20minutesin
1 minute increments
TIM E DELAY ON 2ND ST AG E ECONOMIZI NG
While in the Economizing mode, this is the delay between thermostat
Y2 call and Y1--- O output to mec hanic al cool i ng stage, to all ow high
speed fan operation to attempt to cool space first.