Carrier EconoMiser X - Setpoints Configuration; Menu 3: Setpoints

Carrier EconoMiser X
24 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
Menu 3: Setpoints
Parameter
Project
Value
Parameter
Default
Value
Parameter
Range and Increment
Notes
MAT SET 53_F
(12_C)
38 to 65_F;
(3 to 18_C)
increment by 1_
SUPPL Y AIR SETPOINT
Setpoint determines where the economizer will modulate the OA
damper to maintain the supply air temperature.
SeeMenuNote2(onpage8).
LOW T LOCK 32_F
(0_C)
---45 to 80_F
(---43 to 27_C)
increment by 1_
COMPRESSOR LOW TEMPERATURE LOCK OUT
Setpoint determines outdoor temperature when the mechanical
coo l ing cannot be turned on.
DRYBLB SET 63_F
(17_C)
48 to 80_F;
(9 to 27_C)
increment by 1_
OA DRY BU LB TEMPERATURE CHANGE OVER SETP OINT
Setpoint determines where the economizer will assume outdoor air
temperature is good for free cooling; e.g.: at 63_F(17_C), unit wil l
economize at 62_F (16.7_C) and below and not economize at 64_F
(17.8_C) and abov e . There is a 2_F(1.1_C) deadband.
SeeMenuNote3(onpage8).
ENTH CURVE ES3 ES1, ES2, ES3, ES4,
or ES5
ENTHALPY CHANGEOVER CURVE
(Requi res enthalpy sens or opti o n)
Enthal py boundary “curves” for econom i zi ng using singl e enthal py.
DCV SET 1100ppm 500 to 2000 ppm;
increment by 100
DEM AND CONTROL VENTILA TI ON SETPOINT
Displays only if CO
2
sens o r is conne ct e d. Setpo i nt for Demand Contro l
V e nt i l a t i o n of space . Above the setpo i nt , the OA dampers wil l modul at e
ope n to bring in addit ion al OA to maintai n a spac e ppm lev el belo w
the setpoint.
MIN POS L 6.0 V 2 to 10Vdc ENTI LATION MINIM UM POSI TION A T LOW SPEE D
DisplaysONLYifaCO2sensorisNOTconnected.
MIN POS H 4.4 V 2 to 10Vdc VENTILATION MINIMUM POSITION AT HIGH SPEED
DisplaysONLYifaCO2sensorisNOTconnected.
VENTMAX L 6.0 V 2 to 10Vdc DCV MAXIMUM DAMPER POSITION A T LOW SPEED
(Requires CO
2
sens o r connec te d)
VENTMAX H 4.4 V 2 to 10Vdc DCV MAXIMUM DAMPER POSITION AT HIGH SPEED
(Requires CO
2
sens o r connec te d)
VENTMIN L 3.7 V 2 to 10Vdc DCV MINIMUM DAMPER POSITION AT LOW SPEED
(Requires CO
2
sens o r connec te d)
VENTMIN H 2.8 V 2 to 10Vdc DCV MINIMUM DAMPER POSITION AT HIGH SPEED
(Requires CO
2
sens o r connec te d)
ERV OAT SP 32_F
(0_C)
0to50_F;
(---18 to 10_C)
increment by 1_
ENERGY RECOVERY VENTILATI ON UNIT OUTDOOR AIR
TEMPERATURE SETPOINT
Onl y whe n A UX1 O = ERV
EXH1 L SET 65% 0 to 100%;
increment by 1
EXHAU ST F AN STAGE 1 SETPOINT AT LOW SPEED
Set poi nt for OA damper posit i on when exhaust fan1 is powere d by the
economizer .
EXH1 H SET 50% 0 to 100%;
increment by 1
EXHAUST FAN STAGE 1 SETPOINT AT HIGH SPEED
Set poi nt for OA damper posit i on when exhaust fan1 is powere d by the
economizer .
EXH2 L SET 80% 0 to 100%;
increment by 1
EXHAU ST F AN STAGE 2 SETPOINT AT LOW SPEED
SetpointforOAdamperpositionwhenexhaustfan2ispoweredby
the economizer.
Only used when AUX1--- O is set to EHX2.
EXH2 H SET 75% 0 to 100%;
increment by 1
EXHAUST FAN STAGE 2 SETPOINT AT HIGH SPEED
SetpointforOAdamperpositionwhenexhaustfan2ispoweredby
the economizer.
Only used when AUX1--- O is set to EHX2.
Copyright 2012 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 03/12
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: LLECON---02SI