Carrier EconoMiser X - Page 17

Carrier EconoMiser X
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
Table 11 W7220 Input/Output without CO
2
Sensor
INPUTS
Ref:
FAN
SPD
(a)
OUTPUTS
DEMAND
CONTROL
VENTILATION
OUTSIDE AIR
Good to
economize?
Y 1 --- I Y 2 --- 1
Mechanical Cooling Stage
Occupancy
OCC Yes OCC No
Y 1 --- O / 1 S T Y 2 --- O / 2 N D Outside Air Damper Position
NO CO
2
SENSOR
No
Off Off Low 0 --- v / O f f 0 --- v / O f f MIN POS L Closed
On Off Low 2 4 --- v / O n 0 --- v / O f f MIN POS L Closed
On On High 2 4 --- v / O n 2 4 --- v / O n MIN POS H Closed
Yes
Off Off Low 0 --- v / O f f 0 --- v / O f f MIN POS L Closed
On Off Low 0 --- v / O f f 0 --- v / O f f
Modulating:
MIN POS L to
F u l l --- O p e n
Modulating:
Closed to
F u l l --- O p e n
On On High
2SP DELAY (b);
24v/On
0 --- v / O f f ( c )
Modulating:
MIN POS H to
F u l l --- O p e n
Modulating:
Closed to
F u l l --- O p e n
(a)
Fan Speed for reference only; tins is not an input or ou tput fu nction of the W7220
(b)
See Menu ADV SETU P ---> 2SP FAN DELAY for details
(c)
See Menu ADV SETU P ---> STG# DLY. With Stage 3 delay enabled, control can turn on 2
nd
stage of cooling Y2---O after delay if the call for Y2---I has not
been satisfied.
Table 12 W7220 Input’/Output with Demand Control Ventilation (DCV)
INPUTS
Ref:
FAN
SPD
(a)
OUTPUTS
DEMAND
CONTROL
VENTILATION
OUTSIDE AIR
Good to
economize?
Y 1 --- I Y 2 --- 1
Mechanical Cooling Stage
Occupancy
OCC Yes OCC No
Y 1 --- O / 1 S T Y 2 --- O / 2 N D Outside Air Damper Position
Below set
No
Off Off Low 0 --- v / O f f 0 --- v / O f f VENTMIN L Closed
On Off Low 2 4 --- v / O n 0 --- v / O f f VENTMIN L Closed
On On High 2 4 --- v / O n 2 4 --- v / O n VENTMIN H Closed
Yes
Off Off Low 0 --- v / O f f 0 --- v / O f f VENTMIN L Closed
On Off Low 0 --- v / O f f 0 --- v / O f f
Modulating:
VENTMIN L to
F u l l --- O p e n
Modulating:
Closed to
F u l l --- O p e n
On On High
2SP DELAY (b);
24v/On
0 --- v / O f f ( c )
Modulating:
VENTMIN H to
F u l l --- O p e n
Modulating:
Closed to
F u l l --- O p e n
Above set
No
Off Off Low 0 --- v / O f f 0 --- v / O f f
Modulating:
VENTMIN L to
VENTMAX L
Closed
On Off Low 2 4 --- v / O n 0 --- v / O f f
Modulating:
VENTMIN L to
VENTMAX L
Closed
On On High 2 4 --- v / O n 2 4 --- v / O n
Modulating:
VENTMIN H to
VENTMAX H
Closed
Yes
Off Off Low 0 --- v / O f f 0 --- v / O f f
Modulating:
VENTMIN L to
VENTMAX L
Closed
On Off Low 0 --- v / O f f 0 --- v / O f f
Modulating:
VENTMIN L to
F u l l --- O p e n
Modulating:
Closed to
F u l l --- O p e n
On On High
2SP DELAY (b);
24v/On
0 --- v / O f f ( c )
Modulating:
VENTMIN H to
F u l l --- O p e n
Modulating:
Closed to
F u l l --- O p e n
(a)
Fan Speed for reference only; tins is not an input or ou tput fu nction of the W7220
(b)
See Menu ADV SETU P ---> 2SP FAN DELAY for details
(c)
See Menu ADV SETU P ---> STG# DLY. With Stage 3 delay enabled, control can turn on 2
nd
stage of cooling Y2---O after delay if the call for Y2---I has not
been satisfied.
LLECON--02SI
Downloaded from ManualsNet.com search engine