F96CTN and G96CTN (Series A): Installation, Start-up, Operating, Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
51
A190155
Fig. 60 – Furnace Setup Switches and Description
Table 17 – Cooling
4
and Heating Air Delivery - CFM (Bottom Return
5
with Filter)
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
Unit Size:
0601714
Clg/CF Switch settings External Static Pressure (ESP)
Clg Switches SW2-3 SW2-2 SW2-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Clg Default: OFF OFF OFF 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
CF Switches SW3-3 SW3-2 SW3-1
Low Clg Default: OFF OFF OFF 565 565 555 540 530 See note 4
Cooling Airflow (SW2)
Low Cooling Airflow (SW3)
OFF OFF ON 565 565 555 540 530 See note 4
OFF ON OFF 695 710 715 710 705 700 695 685 680 675
OFF ON ON 940 945 940 935 935 930 920 900 890 875
ON OFF OFF 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
ON OFF ON 1285 1290 1295 1295 1285 1250 1220 1185 1155 1120
ON ON OFF 1400 1370 1340 1310 1280 1245 1215 1185 1150 1115
ON ON ON 1400 1370 1340 1310 1280 1245 1215 1185 1150 1115
Maximum Clg Airflow
2
1400 1370 1340 1310 1280 1245 1215 1185 1150 1115
CF Switches SW3-3 SW3-2 SW3-1
Cont. Fan Default: OFF OFF OFF 565 565 555 540 530 See note 4
Continuous Fan Airflow (SW3)
OFF OFF ON 565 565 555 540 530 See note 4
OFF ON OFF 695 710 715 710 705 700 695 685 680 675
OFF ON ON 940 945 940 935 935 930 920 900 890 875
ON OFF OFF 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
ON OFF ON 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
ON ON OFF 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
ON ON ON 1115 1120 1125 1120 1120 1115 1110 1100 1095 1085
Heating (SW1)
High Heat Airflow
3
1055 1060 1065 1065 1055 1050 1040 1035 1025 1010
Low Heat Airflow
3
750 770 775 775 770 765 755 745 740 735