F97CMN and G97CMN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
16
Side Return Air Inlet 
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. This panel MUST be in place when only side return
air is used. Where required by code, seal bottom closure to furnace with
tape, mastic or other durable sealing method.
NOTE:    Side  return-air openings  can  be  used  in  UPFLOW and some
HORIZONTAL configurations.  Do  not  use  side  return-air  openings  in
DOWNFLOW configuration, see Fig. 20, Fig. 21, Fig. 22.
Downflow Installation
NOTE:    The  furnace  must  be  pitched  as  shown  in  Fig. 18  for  proper
condensate drainage. 
Supply Air Connections 
NOTE:  For downflow applications, this furnace is approved for use on
combustible  flooring when  any  one  of  the following  3 accessories  are
used: 
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Fig. 24.
3. Construct plenum to dimensions specified in Table 4 and Fig. 24.
4. Install special base coil assembly or coil box as shown in in Fig. 24. 
NOTE: It is recommended that the perforated supply-air duct flanges be
completely  removed  from  furnace  when  installing  the  furnace  on  a
factory-supplied cased  coil  or  coil  box. To  remove  the supply-air duct
flange,  use  wide  duct  pliers  or  hand  seamers  to  bend  flange back  and
forth until it breaks off. Be careful of sharp edges, see Fig. 19.
The  return-air  duct  must  be  connected  to  return-air  opening  (bottom
inlet). DO NOT cut into casing sides (left or right). Bypass humidifier
connections should be made at ductwork or coil casing sides exterior to
furnace, see Fig. 21.
Bottom Return Air Inlet 
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used in  downflow applications. To remove bottom closure panel,
see Fig. 23.
Horizontal Installation 
NOTE:  The  furnace must  be pitched  forward  as  shown  in  Fig. 18  for
proper condensate drainage. 
Table 5 – Opening Dimensions - In. (mm)
WARNING
!
FIRE, EXPLOSION, AND CARBON MONOXIDE 
POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage. 
Do  not  install  the  furnace  on  its  back  or  hang  furnace  with  control
compartment  facing  downward.  Safety  control  operation  will  be
adversely  affected.  Never  connect  return-air  ducts  to  the  back  of  the
furnace. 
CAUTION
!
MINOR PROPERTY HAZARD
Failure to follow this caution may result in minor property damage.
Local  codes  may  require  a  drain  pan  under  entire  furnace  and
condensate  trap  when  a  condensing  furnace  is  used  in  an  attic
application or over a finished ceiling. 
FURNACE 
CASING 
WIDTH
IN. (mm) 
APPLICATION 
PLENUM OPENING  FLOOR OPENING 
A  B  C  D 
17–1/2
(445) 
Upflow Applications on Combustible or Noncombustible Flooring 
(subbase not required) 
16
(406)
21-5/8
(549)
16-5/8
(422) 
22-1/4
(565) 
Downflow Applications on Noncombustible Flooring
(subbase not required) 
15-7/8
(403) 
19
(483) 
16-1/2
(419) 
19-5/8
(498) 
Downflow applications on combustible flooring
(subbase required) 
15-1/8
(384) 
19
(483) 
16-3/4
(425) 
20-5/8
(600) 
Downflow Applications on Combustible Flooring with Coil Assembly 
or coil box (subbase not required) 
15-1/2
(394) 
19
(483) 
16-1/2
(419) 
20
(508)
21
(533) 
Upflow Applications on Combustible or Noncombustible Flooring 
(subbase not required) 
19-1/2
(495) 
21-5/8
(549) 
20-1/8
(511) 
22-1/4
(565) 
Downflow Applications on Noncombustible Flooring
(subbase not required) 
19-3/8
(492) 
19
(483) 
20
(508)
19-5/8
(498) 
Downflow applications on combustible flooring
(subbase required) 
18-5/8
(473) 
19
(483) 
20-1/4
(514) 
20-5/8
(600) 
Downflow Applications on Combustible Flooring with Coil Assembly 
or coil box (subbase not required) 
19
(483)
19
(483) 
20
(508) 
20
(508)
24-1/2
(622) 
Upflow Applications on Combustible or Noncombustible Flooring 
(subbase not required) 
23
(584) 
21-1/8
(537) 
23-5/8
(600) 
22-1/4
(565) 
Downflow Applications on Noncombustible Flooring
(subbase not required) 
22-7/8
(581) 
19
(483) 
23-1/2
(597) 
19-5/8
(498) 
Downflow applications on Combustible flooring
(subbase required) 
22-1/8
(562) 
19
(483) 
23-3/4
(603) 
20-5/8
(600) 
Downflow Applications on Combustible Flooring with Coil Assembly 
or coil box (subbase not required) 
22-1/2
(572) 
19
(483) 
23-1/2
(597) 
20
(508)