F97CMN and G97CMN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
31
General
If this furnace replaces a furnace that was connected to a vent system or
chimney, the vent or vent connectors of other remaining appliances may
need to be re-sized. Vent systems or vent connectors of other appliances
must be sized to the minimum size as determined using appropriate table
found in the current edition of National Fuel Gas Code NFPA 54/ANSI
Z-223.1. In Canada, refer to CAN/CSA-B149.1.
An abandoned masonry chimney may be used as a raceway for properly
insulated  and  supported  combustion-air  (when  applicable)  and  vent
pipes. Each  furnace  must  have its own  set  of  combustion-air and vent
pipes and be terminated individually, as shown in Fig. 38 for Direct Vent
(2-Pipe) system or Fig. 41 for ventilated combustion air option.
A  furnace shall not  be connected to a  chimney flue  serving a  separate
appliance designed to burn solid fuel.
Other gas  appliances  with  their  own  venting system  may  also use  the
abandoned chimney as a raceway providing it is permitted by local code,
the current edition of the National Fuel Gas Code and the vent or liner
manufacturer’s installation  instructions. Care must  be  taken to prevent
the  exhaust  gases  from  one  appliance  from  contaminating  the
combustion air of other gas appliances.
Do  not  take  combustion  air  from  inside  the  chimney  when  using
ventilated combustion air or single pipe vent option.
These  furnaces  can  be  vented  as  either  direct  vent  (two-pipe)  or  as
ventilated  combustion  air  system.  Each  type  of  venting  system  is
described  below.  Common  venting  between  these  furnaces  or  other
appliances is prohibited.
Materials
U.S.A.
Combustion  air  and  vent  pipe,  fittings,  primers,  and  solvents  must
conform to American National Standards Institute (ANSI) standards and
American  Society  for  Testing  and  Materials  (ASTM)  standards.  See
Table 11 for approved materials for use in the U.S.A. This furnace is also
CSA  approved  for  venting  with  M&G  DuraVentR  PolyProR
polypropylene venting systems.
Canada
Special Venting Requirements for Installations in Canada Installation in
Canada  must  conform  to  the  requirements  of  CAN/CSA  B149  code.
Vent systems must be composed of pipe, fittings, cements, and primers
listed  to  ULC  S636.  M&G  DuraVent  PolyPro  polypropylene  venting
systems are ULC S636 listed.
NOTE:  When  using  polypropylene  venting  systems,  all  venting
materials used,  including the vent terminations must be from the same
manufacturer.
Venting Systems
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected
to the venting system being placed into operation could result in carbon
monoxide poisoning or death. 
The following steps shall be followed for each appliance connected to
the  venting  system  being  placed  into  operation,  while  all  other
appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as
required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or
the CSA  B149.1 Natural Gas and  Propane Installation Code and
these  instructions.  Determine  that  there  is  no  blockage  or
restriction, leakage, corrosion and other deficiencies, which could
cause an unsafe condition.
3. As far as practical, close all building doors and windows and all
doors  between  the  space  in  which the appliance(s)  connected  to
the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn  on  clothes  dryers  and  any  appliance  not  connected  to  the
venting system. Turn on any exhaust fans, such as range hoods and
bathroom exhausts, so they are operating at maximum speed. Do
not operate a summer exhaust fan.
6. Follow  the  lighting  instructions.  Place  the  appliance  being
inspected  into  operation.  Adjust  the  thermostat  so  appliance  is
operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft
hood relief opening after 5 minutes of main burner operation. Use
the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the
venting system must be corrected in accordance with the National
Fuel  Gas  Code,  ANSI  Z223.1/NFPA  54  and/or  CSA  B149.1
Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the
venting  system  properly  vents  when  tested  as  outlined  above,
return  doors,  windows,  exhaust  fans,  fireplace  dampers  and  any
other  gas-fired  burning  appliance  to  their  previous  conditions  of
use.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure  to  follow  the  instructions  outlined  below  for  each  appliance
being placed into operation could result in carbon monoxide poisoning
or death.
For  all  venting  configurations  for  this  appliance  and  other  gas
appliances  placed  into  operation  for  this  structure,  provisions  for
adequate combustion, ventilation, and dilution air must be provided in
accordance with: 
U.S.A.  Installations:  Current  edition  of  Section  9.3  NFPA  54/ANSI
Z223.1, Air for Combustion and Ventilation and applicable provisions
of the local building codes.
Canadian  Installations:  Current  edition  of  Part  8  of
CAN/CSA-B149.1.  Venting  Systems  and  Air  Supply  for  Appliances
and all authorities having jurisdiction.
NOTICE
!
RECOMMENDED SUPPORT FOR VENT 
TERMINATION
It  is  recommended  that  sidewall  vent  terminations  of  over  24  inches
(0.6 M) in length or rooftop vent terminations of over 36 inches (1 M)
in  length  be  supported  by  EITHER  the  factory  accessory  vent
termination  kit  or  field-supplied  brackets  or  supports  attached  to  the
structure. A  factory  accessory  vent  termination  kit  may  be  used  for
direct vent terminations. Termination kits are available for 2-in. or 3-in.
pipe. See Table 7 for available options.