24VNA6: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
11
Step 12 – Pumpdown & Evacuation
Because  this  system  has  an  inverter  controlled  compressor  the
conventional procedure cannot be used to "pump down" and isolate the
refrigerant into the outdoor unit.  The UI (User Interface) has provisions
to assist in performing this function. Pump Down
1. Connect gages to liquid and vapor or suction capillary service ports
to  monitor  operating  pressures  during  and  at  completion  of  the
procedure.
2. In the "installation and service" menu of the UI (see Fig. 11), go to
"refrigerant  charging"  and  then  "pump  down"  (see  Fig. 11  &
Fig. 12).
3. Pump  down  in  COOL  mode  allows  refrigerant  to  be  isolated  in
outdoor unit. Set desired time period.   Default time period for the
procedure is 120 minutes. See Fig. 22.
4. Select Start on UI to begin the pumpdown process.  Unit will begin
running in selected mode after a brief delay and a status screen will
be displayed.  See Fig. 23.
5. Close the liquid service valve.
6. The  unit  will  run  with  the low  pressure  protection set  to  indicate
pumpdown is complete when the suction pressure drops below 20
psig.  Compressor protections are still active to prevent damage to
the compressor or inverter (high pressure, high current, etc.).  
7. Once system indicates pumpdown complete or failure to complete
shutdown, close vapor service valve.  
8. A  recovery  system  will  be  required  to  remove  final  quantity  of
refrigerant from indoor coil and line set. 
9. Remove power from indoor and outdoor unit prior to servicing unit.
A200040
Fig. 22 – Pump Down Setup Screen
A200041
Fig. 23 – Pump Down Status Screen
Evacuation and Recovery of Refrigerant from within 
24VNA6
Because  the  5  ton  unit  has  an  EXV  for  the  vapor  injection  device,
additional steps must be taken to open the EXV if the OD unit must be
evacuated for service reasons.  If the EXV is  not open when pulling a
vacuum or recovering refrigerant from the OD unit, extended evacuation
time may be required and/or inadequate vacuum obtained.  The UI (User
Interface)  has  provisions  to  open  the  EXV  for  refrigerant  recovery
and/or evacuation.  
1. Connect gages to liquid and vapor or suction capillary service ports
to  monitor  operating  pressures  during  and  at  completion  of  the
procedure.  Attach recovery system or vacuum pump to gage set as
needed for the service procedure.  The service valves must be open
to evacuate the unit through the line set service ports.  The suction
capillary service port is a direct connection to the suction port of the
compressor.
2. In the "installation and service" menu of the UI (see Fig. 11), go to
"refrigerant  charging"  and  then  "evacuation"  (see  Fig. 12)  and
Fig. 13).
3. Set desired  time  period.  Default time  period for the procedure is
120 minutes.  See Fig. 24.
4. Select START on UI to open the valve.
5. Begin  evacuation  or  refrigerant  recovery  as  required  for  the
procedure  after  UI  indicates  the  EXV  is  open.    Power  may  be
removed  from  outdoor  unit  after  the  UI  indicates  "READY  TO
EVACUATE."  See Fig. 25.
6. Remove power from indoor and outdoor unit prior to servicing unit.
The EXV will retain the open position.
NOTE:  See  service  training  materials  for  troubleshooting  the  EXV
using EXV CHECK mode.
A200042
Fig. 24 – Evacuation Setup Screen
A200043
Fig. 25 – Evacuation Status Screen