47
Configuration Screens (cont)
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
DESCRIPTION VALUE* UNITS NAME
OMNIZONE::PRES: Head Pressure(Comp1)
Low Input Endpoint 0.6 Volts LowRange
High Input Endpoint 4 Volts HighRng
Low Conversion Endpoint 6.23 PSIG LowConv
High Conversion Endpoint 309.77 PSIG HighConv
Low Input Fault 0.3 Volts LowFlt
High Input Fault 5 Volts HighFlt
OMNIZONE::RESET: Ext. Supply Air Reset
Low Input Endpoint 2 Volts LowRange
High Input Endpoint 10 Volts HighRng
Low Conversion Endpoint 0 dF LowConv
High Conversion Endpoint 20 dF HighConv
Low Input Fault 0 Volts LowFlt
High Input Fault 10 Volts HighFlt
OMNIZONE::ALARM: Critical Fault
Output Logic Type Normal LogType
Minimum Off Time 4 sec MinOff
Minimum On Time 4 sec MinOn
Delay Time 10 sec DlyTim
OMNIZONE::BPS_S: Bypass Start_Stop
Output Logic Type Normal LogType
Minimum Off Time 60 sec MinOff
Minimum On Time 60 sec MinOn
Delay Time 5 sec DlyTim
OMNIZONE::CMP1: Compressor 1 Relay
Output Logic Type Normal LogType
Minimum Off Time 300 sec MinOff
Minimum On Time 300 sec MinOn
Delay Time 30 sec DlyTim
OMNIZONE::CMP2: Compressor 2 Relay
Output Logic Type Normal LogType
Minimum Off Time 300 sec MinOff
Minimum On Time 300 sec MinOn
Delay Time 30 sec DlyTim
OMNIZONE::CMP3: Compressor 3 Relay
Output Logic Type Normal LogType
Minimum Off Time 300 sec MinOff
Minimum On Time 300 sec MinOn
Delay Time 30 sec DlyTim
OMNIZONE::CMP4: Compressor 4 Relay
Output Logic Type Normal LogType
Minimum Off Time 300 sec MinOff
Minimum On Time 300 sec MinOn
Delay Time 30 sec DlyTim
OMNIZONE::DEHUM: Ext. Dehumidification
Output Logic Type Normal LogType
Minimum Off Time 60 sec MinOff
Minimum On Time 60 sec MinOn
Delay Time 10 sec DlyTim
OMNIZONE::HEAT1: Heat Stage 1
Output Logic Type Normal LogType
Minimum Off Time 60 sec MinOff
Minimum On Time 60 sec MinOn
Delay Time 10 sec DlyTim
OMNIZONE::HEAT2: Heat Stage 2
Output Logic Type Normal LogType
Minimum Off Time 60 sec MinOff
Minimum On Time 60 sec MinOn
Delay Time 10 sec DlyTim
OMNIZONE::HEAT3: Heat Stage 3
Output Logic Type Normal LogType
Minimum Off Time 60 sec MinOff
Minimum On Time 60 sec MinOn
Delay Time 10 sec DlyTim
OMNIZONE::HEAT4: Heat Stage 4
Output Logic Type Normal LogType
Minimum Off Time 60 sec MinOff
Minimum On Time 60 sec MinOn
Delay Time 10 sec DlyTim