6.6.1.1 When TA<13, the compressor stops working. And the outdoor fan will stop delaying for 5
seconds until it operates for 3minutest.
6.6.1.2 When TA15, the outdoor fan operates, and the compressor will restart to operate after
15seconds.
6.6.2. The speed cant be controlled at drying mode, and the indoor fan motor operates at low speed.
6.6.3 Power management (for power management models)
Entering into drying mode, indoor fan motor operates immediately and keeps moving for 30 minutes
at lease. Compressor operates, and indoor fan motor keeps moving; Compressor stops operation,
indoor fan motor shuts off after a delay of 30 minutes.
6.6.4. The ION/TIMER functions are valid at the drying mode.
6.7 Heating mode (heater)
6.7.1. The speed of indoor fan can be optionally chosen as High/Mid/Low.
The compressor and outdoor fan keep on stop (except P1 protection)
6.7.2. At heating mode, the heater will operate according to the difference between TA and TS.
Electric heater operates as below.
6.7.2.1. When TATS, the indoor fan operates firstly, and then the heater operates after 4 seconds.
6.7.2.2. If TATS1, the heater stops. Then the heater turns off after 10 seconds.
When the unit is off at the heating mode, the indoor fan motor stops delaying for 10 seconds
6.7.3. The ION/TIMER functions are valid at the heating mode.
6.8 Heating mode (heat pump)
6.8.1. When TATS+5, compressor operates; When TATS6, compressor stops.
When TA 5 , heat pump mode is invalid, and water pump/indoor motor/outdoor
motor/compressor/ shaded pole motor stop; When TA6, heat pump mode resumes to be valid.