Table 7 — Switch Functions
*Not required on 48FM and 50FM,FS units (units with high capacity power exhaust).
LEGEND
Air Pressure Tubing —
Before options such as inlet
guide vanes (IGV), variable frequency drive (VFD), and/or
modulating power exhaust can operate properly, the pneumatic
tubing for pressure sensing must be installed. Use fire-retardant
plenum tubing (field-supplied). Tubing size depends on type of
control device (see Table 8 below). Tubing must be run from
the appropriate sensing location (in the duct or in the building
space) to the control device location in the unit.
Table 8 — Tubing Size
INLET GUIDE VANES — The tubing for the duct pressure
(DP) control option should sample supply duct pressure about
2
/
3
of the way out from the unit in the main trunk duct, at a
location where a constant duct pressure is desired.
The inlet guide vanes are controlled by a differential pres-
sure switch (DPS). On sizes 034-048, the DPS is located in the
auxiliary control box at the economizer end of the unit (see
Fig. 33). On sizes 054-104, the DPS is located in the supply fan
section. See Fig. 34. Use a nominal
3
/
8
-in. plastic tubing.
SUPPLY FAN VARIABLE FREQUENCY DRIVE — The
tubing for the duct pressure (DP) control option should sample
supply duct pressure about
2
/
3
of the way out from the unit in
the main trunk duct, at a location where a constant duct pres-
sure is desired.
The duct pressure is sensed by a pressure transducer. The
pressure transducer output is directed to the VFD. On 034-048
units the DP transducer is located in the auxiliary control box.
On 054-104 units, the DP transducer is located in the supply
fan section. See Fig. 34. Use a nominal
1
/
4
-in. plastic tubing.
SWITCH
NUMBER
CONFIGURATION VOLTAGE FUNCTION
SW-1
N.C. 115 Deenergize 115-v (OFC, Comp, IFC, Electric Heaters)
SW-2
N.C. 115 Deenergize TRAN7 (Process Board)
SW-3
N.O. 24 Energize EOR (Open Economizer Outside Air Dampers)
SW-4
N.O. 115 Energize IFC and CR-3 (IGV/VFD)
SW-5
N.C. 115 Isolate IFC and PEC for Separate Operation
SW-6
N.O. 115 Energize PEC (Power Exhaust)
SW-7
N.O. 24
Open PED at DPS (48FK,JK and 50FK,JK Units) Force Power Exhaust VFD
to Maximum Speed (48FM and 50FM,FS Units)
SW-8*
N.C. 24 Block Auto-Close at DPS (Due to Low BP)
SW-9A/B
A: N.O.
B: N.C.
115 max Signal Room Terminals to Open (HIR1)
BP
Building Pressure
DPS
Differential Pressure Switch
EOR
Economizer Open Relay
HIR
Heat Interlock Relay
IFC
Indoor Fan Contactor
IGV
Inlet Guide Vane
N.C.
Normally Closed
N.O.
Normally Open
PEC
Power Exhaust Contactor
PED
Power Exhaust Damper
OFC
Outdoor Fan Contactor
VFD
Variable Frequency Drive
OPTION UNITS
NOMINAL TUBE
SIZE (in.)
Inlet Guide Vanes (IGV)
ALL
3
/
8
Supply Fan Variable
Frequency Drive (VFD)
ALL
1
/
4
Modulating Power Exhaust
FK,FKX,JK,JKX
3
/
8
FM,FS
1
/
4

Table of Contents