Table 1 Physical Data
UNIT SIZE 24040 24060 30040 30060 36060 36090 42060 42090
NOMINAL CAPACITY (ton) 2 2 2 --- 1 /2 2 --- 1 /2 3 3 3 --- 1 /2 3 --- 1 /2
SHIPPING WEIGHT** lb.
SHIPPING WEIGHT** (kg)
352
160
352
160
359
163
359
163
455
206
455
206
455
206
455
206
COMPRESSORS
Quantity
Scroll
1
REFRIGERANT (R --- 410A)
Quantity lb.
Quantity (kg)
6.4
2.9
6.4
2.9
8.3
3.8
8.3
3.8
8.1
3.7
8.1
3.7
8.7
3.9
8.7
3.9
REFRIGERANT METERING DEVICE TXV
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
1..21
13.6
1...21
13.6
2...21
13.6
2...21
13.6
2...21
13.6
2...21
13.6
2...21
13.6
2...21
13.6
OUTDOOR FAN
Nominal CFM
Diameter in.
Diameter (mm)
Motor Hp (Rpm)
2500
24
609.6
1/10 (810)
2500
24
609.6
1/10 (810)
2700
24
609.6
1/5 (810)
2700
24
609.6
1/5 (810)
3000
26
600.4
1/5 (810)
3000
26
600.4
1/5 (810)
3000
26
660.4
1/5 (810
3000
26
660.4
1/5 (810)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
3...17
3.7
3...17
3.7
3...17
3.7
3...17
3.7
3...17
4.7
3...17
4.7
3...17
4.7
3...17
4.7
INDOOR BLOWER
Nominal Low Stage Cooling Airflow (Cfm)
Nominal High Stage Cooling Airflow (Cfm)
Size in.
Size (mm.)
Motor HP (RPM)
600
600
750
750
900
900
1050
1050
600
800
10x10
254x254
1/2 (1050)
600
800
10x10
254x254
1/2 (1050)
75
0
1000
10x10
254x254
1/2 (1050)
75
0
1000
10x10
254x254
1/2 (1050)
900
1200
11x10
279.4x254
3/4 (1000)
900
1200
11x10
279.4x254
3/4 (1000)
10
5
0
1400
11x10
279.4x254
3/4 (1075)
10
5
0
1400
11x10
279.4x254
3/4 (1075)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas (Factory Installed)
Propane Gas
2...44
2...55
3...44
3...55
2...44
2...55
3...44
3...55
208/230
VAC Models
3...44
3...55
460 VAC
Models
2…38
2…53
3…38
3…53
208/230
VAC Models
3...44
3...55
460 VAC
Models
2…38
2…53
3...38
3...53
HIGH ---PRESSURE SWITCH
(psig) Cut---out Reset (Auto)
650 +/ --- 15
420 +/ --- 25
L O S S --- O F --- C H A R G E / L O W --- P R E S -
SURE SWITCH (Liquid Line) (psig) cut---
out Reset (auto)
5 0 + / --- 7
9 5 + / --- 7
RETURN --- AIR FILTERS}
Throwaway Si ze in.
(mm)
20x20x1
508x508x25
20x24x1
508x610x25
24x30x1
610x762x25
*Based on altitude of 0 to 2000 ft ( 0 ---610 m).
{ Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating air-
flow velocity of 300 ft/minute for throwaway type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.
} If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
48VG

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier Performance 48VG-E and is the answer not in the manual?

Carrier Performance 48VG-E Specifications

General IconGeneral
BrandCarrier
ModelPerformance 48VG-E
CategoryAir Conditioner
LanguageEnglish

Related product manuals