Fig. 41—Short Vent (5 to 8 ft) System
A05094
HORIZONTAL TO ROOF HORIZONTAL TO SIDEWALL
VERTICAL TO SIDEWALLVERTICAL TO ROOF
VENT PIPE
VENT PIPE
VENT PIPE
VENT PIPE
12 MIN
12 MIN
12 MIN
12 MIN
NOTE: A 12-In. minimum offset pipe section is recommended with
short (5-ft. to 8-ft) vent systems. This recommendation is to
reduce excessive condensate droplets from exiting the vent pipe.
COMBUSTION AIR
PIPE (NON-DIRECT
VENT/1-PIPE)
COMBUSTION AIR
PIPE (DIRECT VENT
/2-PIPE)
COMBUSTION AIR
PIPE (NON-DIRECT
VENT/1-PIPE)
COMBUSTION AIR
PIPE (DIRECT
VENT/2-PIPE)
COMBUSTION AIR
P
IPE (NON-DIRECT
VENT/1-PIPE)
COMBUSTION AIR
PIPE (DIRECT VENT
/2-PIPE)
COMBUSTION AIR
PIPE (NON-DIRECT
VENT/1-PIPE)
COMBUSTION AIR
PIPE (DIRECT VENT
/2-PIPE)
Fig. 39—Combustion-Air and Vent Pipe Diameter
Transition Location and Elbow Configuration
A93034
FURNACE
PIPE DIAMETER
TRANSITION IN
VERTICAL SECTION
NOT IN
HORIZONTAL
SECTION
Fig. 40—Air Intake Housing Plug Fitting Drain
A05093
COMBUSTION-AIR
PIPE (DIRECT
VENT/2 PIPE)
BURNER
BOX
COMBUSTION – AIR
INTAKE HOUSING
3/8 ID TUBE
TRAP
TO OPEN
DRAIN
3/16
DRILL
4MIN
COMBUSTION-AIR
PIPE (NON-DIRECT
VENT/1-PIPE)
38