Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48EJ - Base Unit Dimensions, 48 EW,EY038-048

Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48EJ
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VFD Variable Frequency Drive
NOTES:
1. Weights include economizer (STD).
2. Center of gravity.
3. Do not locate adjacent units with flue discharge facing economizer
inlet. Minimum clearances to be:
Adjacent Units: 158-09
Top of Units: No overhang
Condenser Coil: 48-09
Economizer Side: 68-09
Gas Heat Side: 48-09
Filter Access Side: 108-09 (For Removal of Evaporator Coil)
4. For smaller service and operational clearances, contact Carrier
Application Engineering department.
5. Dimensions are in inches.
6. For side-supply/return applications, a single return and supply duct-
work connection is recommended for covering both return and both
supply openings.
UNIT
SIZE
OPERATING
WEIGHT
A B CORNER WEIGHT (lb)
lb ft-in. ft-in. 1 2 3 4
48EW,EYD038 4442 7- 8
11
16
3-10
7
8
1021 894 1180 1347
48EWE038 4602 7-10
1
8
3-11
3
16
1080 934 1200 1388
48EW,EYD044 4668 7- 5
5
16
3-10
7
8
1033 906 1275 1455
48EWE044 4828 7- 6
13
16
3-11
3
16
1094 945 1293 1496
48EW,EYD048 4955 7- 3
11
16
3-10
1
2
1068 953 1384 1550
48EWE048 5115 7- 5
3
16
3-10
13
16
1129 994 1401 1592
Fig. 6 Base Unit Dimensions, 48EW,EY038-048