EasyManua.ls Logo

Carrier WeatherMaker 38YDB - Compressor and Thermistor Operation; Final Checks and Maintenance; Final Installation Checks

Carrier WeatherMaker 38YDB
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Compressor Control Contactors
Low and High capacity contactor coils are 24 volts. The electronic
control board controls the operation of the low speed (C-L) and the
high speed (C-H) contactors.
TEMPERATURE THERMISTORS
Thermistors are electronic devices which sense temperature. As
the temperature increases, the resistance decreases. Thermistors
are used to sense outdoor ambient and coil temperature. Refer to
Fig. 16 for resistance values versus temperature.
If the outdoor ambient thermistor or coil thermistor should fail, a
fault code appears at electronic control. The crankcase heater is
turned on during all off cycles.
IMPORTANT: OUTDOOR AIR THERMISTOR PLACEMENT
Mount outdoor air thermistor underneath unit base pan lip on
control box side of unit as shown in Fig. 17. Attach to base pan
with adhesive tape or other field expedient means.
IMPORTANT: If outdoor air thermistor is not properly placed
underneath base pan, unit may have nuisance thermistor out of
range faults.
Step 14Final Checks
IMPORTANT: Before leaving job, be sure to do the following:
1. Ensure that all wiring and tubing is secure in unit before
adding panels and covers. Securely fasten all panels and
covers.
2. Tighten service valve stem caps to 1/12-turn past finger tight.
3. Leave Users Manual with owner. Explain system operation
and periodic maintenance requirements outlined in manual.
4. Fill out Dealer Installation Checklist and place in customer
file.
Fig. 15Control Board
A00379
CEBD430439-03A
SS0ID
PL1 PL2
HP/AC
SEV
RVS
C
HI
LO
PL3
PL4
PL5
OCT OAT HPS LPS
PWM2
PWM1
BRN
BLU
BLK
YEL
RED
CCH L2 ODF VH VC
CESO130078-00
K1
CEPL130439-01
COMM STATUS
D51
D52
A B C D
0
Y2
Y1
W1
C
R
120
30
60
60
30
90
DEFROST
TIME (MIN)
R39
R44
R42
C18
C16
R36
FORCED
DEFROST
1
1
1
S1
R89
R91
R87R86
R85
J1
C31
R61
R65
R38
R33
C2
R9
1 2
Table 10Factory Defaults
FAILED COMPONENT FUNCTION DEFAULT
Ambient Thermistor
Defrost Initiation
Defrost is initiated based on coil
temperature and time.
One minute fan off dealy in cooling
greater than or equal to 100°F
No delay function
Outdoor Coil Thermistor Defrost Initiation and Termination
Defrost occurs at each time interval, but
terminate after 5 minutes
Table 11Two-Speed Compressor
(Winding Resistance at 70°F±20°)
WINDING 2 TON 3 TON 4 TON 5 TON
Start (S-C) 2.280 1.850 1.459 0.740
Run (R-C) 0.770 0.745 0.552 0.356
21

Related product manuals