Fig.
16
Suction
Line
Piping
Row-Split
Coil
"DRILL
&
SCREW
PAN
TO
COVER
SHEET
DRILL
$'
HOLE
FOR
TUBE
IN
COIL
COVER
SHEET
CONDENSATE
PAN
Fig.
17
Expansion
Valve
Condensate
Pan
CHILLED
WATER,
HOT
WATER
AND
STEAM
COILS
1.
Use
unions
or
flanged
coil
connections
for
ease
of
service
per
Fig.
18.
2.
Install
a
tee
with
a
pipe
plug
at
coil
connection
to
facilitate
air
blow
thru
coil
for
freeze
protection
per
Fig.
18.
CONDENSATE
DRAIN
Connect
drain
line
and
trap
per
Fig.
19
to
condensate
drain
connection.
Do
not
reduce
pipe
size.
Run
drain
line
to
nearest
open
site
drain.
On
unit
sizes
070
thru
140,
install
a
field-supplied
cap
on
unused
drain
connection.
18
HUMIDIFIERS
Humidifier
water
and
steam
supply
must
be
odor-free
and
uncontaminated.
Consideration
shall
be
taken
by
installer
as
to
corrosive
and
odor
effect
from
hard
or
contami-
nated
water.
Carrier
assumes
no
responsibility
for
problems
caused
by
inadequate
water
treatment.
General
It
is
recommended
that
a
strainer
be
installed
in
supply
line.
Steam
grid
humidifiers
require
a
drain
line
trap
with
a
water
seal
to
offset
unit
negative
static
pressure.
Trap
is
similar
to
that
shown
in
Fig.
19.
Fig.
18
Coil
Connections

Other manuals for Carrier WEATHERMAKER 39B