EasyManua.ls Logo

Carrier WEATHERMAKER 48/50AJ - Page 119

Carrier WEATHERMAKER 48/50AJ
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
119
Table 116 — Economizer Control Board (ECB1) Inputs and Outputs
POINT
NAME
POINT DESCRIPTION
I/O POINT
NAME
PLUG AND PIN
REFERENCE
SIGNAL PIN(S) PORT STATE
INPUTS
RMTIN Remote occupancy DI1 J4, 1-2 2 24VAC = 1, 0VAC = 0
ECONENBL,
ECOORIDE
Economizer enable DI2 J4, 3-4 4 24VAC = 1, 0VAC = 0
RARH Return air relative humidity AN1 J5, 1-3 1=24VDC, 2=0-20mA in, 3=GND 0-20mA
OARH Outdoor air relative humidity AN2 J5, 4-6 4=24VDC, 5=0-20mA in, 6=GND 0-20mA
OUTPUTS
ECB1_AO1 ECB1, analog output 1 AO1 J9, 1-2 1=0-20mA, 2=GND 0-20mA OUT
ECONOCMD
Economizer actuator
(digital control)
PP/MP J7, 1-3 1=PP/MP Data, 2=24VAC, 3=GND Belimo PP/MP Protocol
PE_A Power Exhaust stage A RLY1 J8, 1-3 1 = 2 = RLY1A, 3 = RLY1B 1 = Closes RLY1A/RLY1B
PE_B Power Exhaust stage B RLY 2 J8, 4-6 4 =5 = RLY2A, 6 = RLY2B 1 = Closes RLY2A/RLY2B
PE_C Power Exhaust stage C RLY 3 J8, 7-9 7 = 8 = RLY3A, 9 = RLY3B 1 = Closes RLY3A/RLY3B
ECON_PWR Economizer Power RLY 6 J8, 16-18 16 = 17 = RLY6A, 18 = RLY6B 1 = Closes RLY6A/RLY6B
Fig. 27 — Economizer Control Board (ECB1) and VAV Control Board (ECB2)
A48-7706

Table of Contents