APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST
NAME READ/WRITE UNITS RANGE OBJECT NAME OBJECT ID
AIRSIDE LINKAGE STATUS R
"0=NOT ACTIVE
1=ACTIVE"
a_link_status_1 BV:2601
(AIRSIDE LINKAGE) INDOOR AIR QUALITY R ppm 0 to 5000 link_iaq_1 AV:2607
(AIRSIDE LINKAGE) MAX DAMPER POSITION R % 0 to 100 link_max_dmpr_1 AV:2611
(AIRSIDE LINKAGE) SPACE RELATIVE HUMIDITY R % 0 to 100 link_rh_1 AV:2606
AIR TEMP LVG SUPPLY FAN F sat_1AV:10
AIRSIDE LINKAGE ALARM R
"0=NORMAL
1=ALARM"
air_linkage_fail_1 BV:7030
ALARM STATE R
"0=NORMAL
1=ALARM"
alm_1 BV:9
BUILDING PRESSURE R H2O bldg_static_press_1 AV:1070
BUILDING PRESSURE SETP. R/W H2O -0.25 to 0.25 bldg_press_stpt_1 AV:3070
CIR A DISCHARGE PRESSURE R psig discharge_press_a_1 AV:1601
CIR A SAT. CONDENSING TEMPERATURE R °F sat_cond_temp_a_1 AV:1602
CIR A SAT. SUCTION TEMPERATURE R °F sat_suction_temp_a_1 AV:1603
CIR A SUCTION PRESSURE R psig suction_press_a_1 AV:1600
CIR B DISCHARGE PRESSURE R psig discharge_press_b_1 AV:1605
CIR B SAT. CONDENSING TEMPERATURE R °F sat_cond_temp_b_1 AV:1606
CIR B SAT. SUCTION TEMPERATURE R °F sat_suction_temp_b_1 AV:1607
COMPRESSOR A1 RELAY R
"0=OFF
1=ON"
cmpa1_1 BV:16
COMPRESSOR A2 RELAY R
"0=OFF
1=ON"
cmpa2_1 BV:17
COMPRESSOR B1 RELAY R
"0=OFF
1=ON"
cmpb1_1 BV:18
COMPRESSOR B2 RELAY R
"0=OFF
1=ON"
cmpb2_1 BV:19
CONTROLLING RETURN TEMP R/W °F -40 to 240 ra_temp_1 AV:1030
CONTROLLING SPACE TEMP R/W °F -40 to 240 space_temp_1 AV:2007
COOLING CONTROL POINT R °F cool_ctrl_point_1 AV:1024
COOLING OCCUPIED SETPOINT R/W °F 40 to 99 occ_cl_stpt_1 AV:3001
COOLING UNOCCUPIED SETPOINT R/W °F 40 to 99 unocc_cl_stpt_1 AV:3003
CTL.TEMP RAT,SPT OR ZONE - PRIME VARIABLE R °F ctrltemp_1 AV:43
CURRENT RUNNING CAPACITY R % cool_capacity_1 AV:1023
CURRENT RUNNING CAPACITY R % htsg_cap_1 AV:44
DEHUMIDIFY COOL SETPOINT R/W °F 40 to 55 dhcoolsp_1 AV:49
DEHUMIDIFY INPUT R/W
"0=OFF
1=ON"
dhdiscin_1 BV:30
DEHUMIDIFY RH SETPOINT R/W % 10 to 90 dhrelhsp_1 AV:50
DEMAND LIMIT SW.1 SETPT. R/W % 0 to 100 dlswsp1_1 AV:53
DEMAND LIMIT SW.2 SETPT. R/W % 0 to 100 dlswsp2_1 AV:54
ECONOMIZER ACT. CURR. POS R % econ_pos_1 AV:1028
ECONOMIZER ACTIVE? R
"0=OFF
1=ON"
ecactive_1 BV:36
ELEMENT COMM STATUS R
"0=NO COMM
1=NORMAL"
element_stat_1 BV:2999
EVAPORATOR DISCHARGE TMP R °F edt_1 AV:76
EXHAUST FAN VFD SPEED R % ef_vfd_output_1 AV:2075
FILTER STATUS INPUT R/W
"0=CLEAN
1=DIRTY"
filter_status_1 BV:1052
HEAT RELAY 1 R
"0=OFF
1=ON"
hs1_1 BV:52
HEAT RELAY 2 R
"0=OFF
1=ON"
hs2_1 BV:53
HEAT-COOL SETPOINT GAP R/W °^F 2 to 10 hcsp_gap_1 AV:83
HEATING CONTROL POINT R °F heat_ctrl_point_1 AV:1025
HEATING OCCUPIED SETPOINT R/W °F 40 to 99 occ_ht_stpt_1 AV:3002
HEATING SUPPLY AIR SETPT R/W no unit 80 to 120 saspheat_1 AV:3008
HEATING UNOCCUPIED SETPOINT R/W °F 40 to 99 unocc_ht_stpt_1 AV:3004
HVAC MODE NUMERICAL FORM R no unit hvac_mode_1 AV:1022
IAQ - DISCRETE INPUT R/W
"0=LOW
1=HIGH"
iaq_status_1 BV:1050
IAQ - PPM INDOOR CO2 R/W no unit 0 to 5000 iaq_1 AV:1009
LEAVING AIR TEMPERATURE F lvg_air_temperature_1 AV:1027