EasyManua.ls Logo

CellarPro 1800XT - Page 26

CellarPro 1800XT
31 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V5.17
25
Alarms
The cooling unit has both an audible notification and a visual alarm indicator (shown
in “red” on the control panel) that are activated when an alarm is triggered. Please
note: the HA and LA alarms are disabled during the first 23 hours of operation after
the cooling unit is plugged in and/or turned on.
The control panel also will flash a code for each alarm, as follows:
Alarm Code What it means
What to do
P1, P3 Probe Failure
Call CellarPro at 877.726.8496
HA
The temperature
inside the cellar is too
warm (above 70°F for
more than 1 hour)
Check seals;
Check if door was left open;
Lower the ambient temperatures
HA2
The condenser
temperature is too
high (above 140°F)
Check that the condenser fan (at
the rear of the cooling unit) is
operating;
Make sure that the filter (if used)
or coils are clean;
If the unit is ducted, make sure
that the auxiliary fan is operating;
Check for any blockages of the hot
air intake or exhaust
Then turn off the unit immediatel
y
and call CellarPro at 877.726.8496
or email info@cellarpro.com
LA The temperature
inside the cellar is too
cold (below 45°F)
Raise the ambient temperature;
Make sure the cold air discharge
has sufficient clearance for the air
to circulate
Raise the “Minimum Set Point”
LA2 The temperature at
the condenser coils
(outside the cabinet)
has dropped below the
alarm temperature
setting
Call CellarPro at 877.726.8496