II. Overview
CellarPro Cooling Capacity*
Each of our cooling units includes sizing guidelines that are based on R19 insulation
throughout the cellar and 85F peak ambient temperatures outside the cellar.*
To find the BTUH output for each of our 1800 cooling units at 55F and 60F, and the
thermal loads for various-size cellars, refer to the table below. In order to maintain your
desired cellar temperature, the cooling unit’s BTUH output (at 55F or 60F inside the cellar)
must be greater than the load of your cellar, as shown in the body of the table.
*If your cellar is constructed with glass, or has uninsulated walls, or does not have a vapor
barrier),
the thermal load will be much higher than what’s shown in the table. In this
case, please .visit http://www.cellarprocoolingsystems.com/request-thermal-load to
request a customized thermal load calculation for your cellar:
Cellar Temp
55 Degrees 60 Degrees
BTUH 1800QTL
1065 1154
BTUH 1800QT
1380 1479
BTUH 1800XT
1456 1558
BTUH 1800XTS / XTSx
1886 2031
Cellar Insulation –
Walls, ceiling & floor*:
R-12
R-19
R-12
R-19
Cellar Size Ambient Temp
75 Degrees
1068 979 940 862
100 Cu Ft. 85 Degrees
1180 1046 1038 920
95 Degrees
1291 1114 1136 980
75 Degrees
1380 1253 1214 1103
200 Cu Ft. 85 Degrees
1538 1349 1353 1187
95 Degrees
1699 1446 1495 1272
75 Degrees
1700 1542 1496 1357
300 Cu Ft. 85 Degrees
X 1562 1672 1463
95 Degrees
X 1909 2003 1558
75 Degrees
X 1744 1690 1535
400 Cu Ft. 85 Degrees
X 1879 1888 1654
95 Degrees
X X X 1773