DissipationTime”fromAutotoarecommendedvalueof180seconds(3minutes).Thetimecan
besetfrom0to900secondsin30secondincrements.
HumidityManagementwithOtherThermostats:ourNTUpdateKitispre‐programmedwitha
fixed“fanoffdelay”of3minutes.Therefore,attheendofeachcoolingcycle,thecoolingunit
fanswillcontinuetorunfor3minutes.
TemperatureDisplayonCoolingUnit
ThetemperaturedisplayprovidedonthecoolingunitenhancesthefunctionalityoftheNTforwine
cellarapplications.Alarmstriggeranaudiblealarmonlyatthecoolingunit,thealarmsarenot
communicatedthroughtheNT.ConsultthecoolingunitOwner’sManualfordetailed
troubleshootinginformationrelatedtothesealarms.
The“Set”buttonhasnoeffectsincethesetpointismanagedbytheNT.
ThefollowingparametersandfunctionsarenotavailablewiththeNTconfiguration:HY,FON,
SET,HES,QuickChillandEnergySaver.
Forself‐containedcoolingunits,highandlowambienttemperaturealarms(“HA2”/”LA2”)will
behaveasfollows(refertothecoolingunit’sOwner’sManualforadditioninformation):
“HA2”alarm‐thecompressorwillshutdownuntilitcoolsoff.
“LA2”alarm‐willnotshutdowntheunitandcontactCellarProasap.
Astartupsafetydelayof3minutesisenabledwhenpowerisfirstsuppliedtotheunit,orwhen
recoveringfromapowerfailure.
Thedefrostcyclewillbemanagedautomaticallybasedontheunitconfiguration.Whenthe
coolingunitisindefrost,“DEF”isshownonthedisplay.
Thepowerbuttoncanbeusedtoturnofftheunit.Whenthedisplayreads“OFF”,the
compressorandfansareturnedoff,howevertheNTstillhas24VACpower.
Tocompletelyshutdownthesystem,turnoffboththecoolingunitandtheNT,ordisconnect
powertothecoolingunit.