35V3.15.22
HA2AlarmHasBeenTriggered
Thecoolingunitisdesignedto measurethe temperatureofthecondensercoilsand,ifthe
temperatureexceeds130
°
F,theHA2alarmwilldisplayonthecontrolpanel.
Ifthisalarmhappens
whenyoufirstreceiveandstartoperatingyourCellarProcoolingunit
,
turnthefantothe“High”setting,checkforappropriateinstallationandventilationontheHot
Sideofthecoolingunit(ChapterII).Also,makesurethattherearen’tanyobstructionstothe
intakeand/orexhaustvents.
Ifthecoolingunithasbeenoperatingforseveralmonthswithoutanyproblemsandthealarm
occurs:
1. Turnthefanswitchtothe“High”fanspeed.
2. Turn“off”thecondensateevaporatorswitch.
3. Thereare2independentfansinthecoolingunit.Makesurethatthecondenserfan(at
therearofthecoolingunit)isoperating.
4. Makesurethatthefilter(ifused)orthecoilsareclean.
5. Checkforanyblockagesofthehotairintakeorexhaust.
6. IfthecoolingunitisaVSx(ieexternal)unit,thehoodshouldbeshaded.
Ifyourunitcontinuestohaveissues,turnoffthecoolingunitandcallCellarProat877.726.8496or
emailinfo@cellarpro.com
.
LA2Alarmhasbeentriggered
Asnotedabove,thecoolingunitisdesignedtomeasurethetemperatureofthecondenser
coilsand,ifthetemperaturedropsbelowacertainpoint,theLA2alarmwilldisplayonthe
controlpanel.PleasecallCellarProat877.726.8496ifthisalarmoccurs.
CoolingUnitWon’tTurnOn
Thecoolingsystemisprogrammedwitha
3‐MinuteDelay
atStartup
toprotectitsinternal
components.