FanSpeedGuidelines

Non‐Ducted
VSiUnits VSxUnits
Minimum
FanSpeed
Temperatureoffreshairintake <=95F <=90F
Low

Temperatureoffreshairintake <=100 <=95 Medium

Temperatureoffreshairintake <=105 <=100 High

Notes: 1.Thetableassumesthatproperspaceandairflowexistonthehotsideofthecoolingunit
2.Ductedunitsmustalwaysusethehighfanspeed.
3.Werecommendusingthehighfanspeedduringthefirstweekafterinstallation.
Ventilation
AdequateventilationiscriticallyimportantfortheproperoperationofyourCellarProcoolingunit.
OUTSIDETHECELLAR
(TheHotSide‐attherearofthecoolingunit)
CondenserAirExhaust.CellarPro3200VSand4200VSSeriescoolingunitscreatesignificanthotair
whichmustbeexhaustedintoanappropriately‐sizedspacesothatthehotairexhaustcandissipate.
Ifthespaceisconstrainedand/ortoosmall,theheatwillnotdissipate.Inthisevent,thecooling
unitwillbeforcedtore‐circulateitshotairexhaustand/orthestaticpressurewillbackupthe
cooling unit. If this happens, the cooling unit’sability to create cold air inside the cellar will be
compromised.
CondenserAirIntake.Thecondensercoilsrequireaccesstocoolairsothatthecoolingunitcan
producecoldair.Inaddition,thecoolingunitmustbeinstalledsothat,afteritsinstallation,the
condensercoilsareaccessibleforperiodiccleaningorreplacingofthefilter.
Therearofthecoolingunitmustbeinstalledinaspacethatisatleastaslargeasthewinecellar
unlesstherearintakeandexhaustareducted.Boththefrontandtherearofthecoolingunit
requireaminimumclearanceof8inches.
Ducting.Weofferductkitsthatallowthecondenserairintakeand/orexhausttobeductedupto
50 equivalent feet each with a minimum of 8” diameter ducting from start to finish, or 100
equivalentfeeteachwithourauxiliaryfanand8”diameterductingfromstarttofinish.Ourhot
sideductkits(soldseparately)attachtotherearofthecoolingunitandMUSTbeusedwhenducting
ourcoolingunits.TheHIGHfanspeedmustalwaysbeusedwhenductingthecoolingunit.Using
customductadaptersinsteadoftheCellarProductkits,reducingductingbelow8”diameter,using
fansatlowormediumfanspeed,and/orexceedingthe equivalent length limits will impair the
performanceandlongevityoftheunitandvoidthemanufacturer’swarranty.