Do you have a question about the Chandler Systems DROP CS125 Series and is the answer not in the manual?
The DROP Commercial Control Valve Manual describes the CS125 and CS150 Series valves, which are fully automatic control mechanisms designed for water treatment units. These valves are engineered for ease of serviceability, featuring hand-tighten nuts for inlet, outlet, drain, and water meter access, and quick-access plug-in style for the injector or brine port. Accessing the piston and seals requires removing only five Philips head screws and separating a few plastic clips.
The DROP 1.25" and 1.5" valves direct and regulate all cycles of a water treatment unit. They are designed to improve water quality, provide leak detection, and offer water conservation benefits. The system can operate locally without an internet connection or send mobile alerts when connected to a WiFi network, allowing for remote monitoring and adjustments via a mobile device.
The manual provides a quick reference table with detailed specifications for various DROP models (20125X500, 20125X600, 20125X550, 20125X650, 20150X500, 20150X600, 20150X550, 20150X650). These models vary in their piston type (hard water bypass or no hard water bypass during regeneration), injector/plugs configuration, and valve body (CS125 or CS150).
The control valve offers two piston options: a hardwater bypass piston (typical for single tank softening systems, allowing hard water bypass during regeneration) and a non-hardwater bypass piston. All pistons feature a patented water shutoff position to protect properties from water damage. When combined with the non-hardwater bypass piston, commercial DROP valves can be used in parallel without external shut-off valves, providing continuous water treatment.
An integral turbine flow meter allows the DROP system to properly protect a property and notify the end user of usage and potential problems. This meter is quick to access and calibrated for excellent accuracy above 0.75 gallons per minute. An optional combination turbine flow meter and pressure sensor can replace the standard flow meter, monitoring system water pressure at the outlet of the valve.
The DROP system is designed for easy installation, setup, and maintenance. The DROP app provides user control, information, and history of the water treatment system. The app's user interface includes info icons to explain features. Settings relevant to the 1.25" and 1.5" valves are found on the "System > Settings" page and the "Devices > Softener" or "Devices > Filter" pages.
Valve operation is indicated by changing LED colors during regeneration steps. Lights slowly fade from side to side when the valve is in a step, and rotate when moving to a new position.
The DROP valve board is factory preset for most installations: Softeners (device #1), Backwashing filters (device #2), and Aeration valves (device #3). Users can change the valve type (Softener, Backwashing filter, Aeration filter), device number (1-4), and softener resin capacity (45k, 60k, 75k, 90k, 120k, 150k, 210k, 300k, 450k grains capacity). This is useful for replacing boards or configuring systems with multiple treatment steps of the same device type in series.
The valve is designed for easy service. The inlet, outlet, drain, and water meter access points use hand-tighten nuts. The injector or brine port plug is a quick-access, plug-in style with a clip. Piston and seal access requires removing five Philips head screws and separating plastic clips.
To connect brine tubing: ensure the 3/8" tubing is cut squarely and push it 7/8" into the fitting, past the O-ring seal. To release brine tubing: remove the orange locking clip, push in on the gray ring surrounding the brine tube, and pull out the brine tube.
Chandler Systems Inc. provides a limited warranty for DROP Water Management Systems, extended only to the original purchaser or first user for single-family home use. Warranty periods vary by component:
The warranty covers defects in material and workmanship at the time of manufacture. It does not cover media and/or cartridge filter elements, labor costs, shipping charges, or issues arising from improper installation, operation, maintenance, abuse, or environmental conditions outside recommended limits. Claims must be submitted within 30 days of warranty expiration with prompt notice to an authorized DROP Dealer or Chandler Systems.
| Brand | Chandler Systems |
|---|---|
| Model | DROP CS125 Series |
| Category | Control Unit |
| Language | English |