P-Parameters
P83 night mode ending point 0-23(for relative time) 6
P88 Model selection 0~255 4
P94 Whether to use high and low pressure transmitter 0 Disabled; 1 Used 0
P95 temperature difference to control C4 water pump
speed
2~8 5
P96
EEV min open degree
70
P97
Forced sterilization
0,normal;1,forced;(Automatic recovery of 0
after execution)
0
P98
System parameter recovery
0 normal; 1 Recovery (automatically reset 0 after
one execution)
0
P99
Compressor manufacturer 2
101
P100
Virus killing function validation P100=0 Invaid; 1 valid 0
P101
EEV Max manual open
300-500 default:430
480
P102
Defrosting EEV manual open
350
P103
AC electric heater Power W
0-99999w default:5000
5000
P104
C or F degree 0:C degree; 1:F degree
P105
Heat recovery function validation
0:Invalid; 1:valid
P106
AC heater rated voltage
0-500V
220
P107
AC heater transfer coefficient
100-600WF
500
P108
AC Voltage compensation
0
P109
Cooling Inlet Target temp range P109=0:10~25C. P109=1:5~25C(Must use
glycol no frozen at -10C).
P110
AC heating minimum frequency 30~50hz
30hz
P111
DIN6 DIN7 switch
Disable
P112
AU-Mode enable bit
Disable