C Parameters
C42 Heating Method 2 target temperature -30~97
C43 Running returning lubrication oil function. 1On 0 Off
C44 fan type 0AC fan1EC fan
C45 EC fan motor 1 speed 0~3000
C46 EC fan motor 2 speed 0~3000
C47 water pump types 0AC WATER PUMP1EC WATER PUMP
C48 water pump1 speed 1~10 (10 means 100%)
C49 water pump2 speed 1~10 (10 means 100%)
C50 Inductor AC Current value 0~50A
C51 Driver working status value Hexadecimal values
C52 Compressor shut down Code Hexadecimal values
C53 Driver allowed highest frequency 30-120Hz
C54 Reduce frequency temperature setting 55~200
C55 input AC Voltage value 0~550V
C56 input AC current value 0~50AIPM Check, if C56>18A, show F5
C57 Compressor phase current value(Compressor U,V,W
wire DC current)
0~50AIPM Check, show F4 on error
C58 Bus line voltage 0~750V
C59 Fan shutdown Code Hexadecimal values
C60
IPM temp
55~200
C61
Compressor total running time
0~65000 hour
C62
E-heater Compensation power
0~65000W
C63
din6 AC heating mode switch
0=OPEN; 1=CLOSE.
C64
din7 AC cooling mode switch
0=OPEN; 1=CLOSE.