run command is canceled once, and the inverter will respond only after the run command becomes valid again.
8.9.2 Motor overload protection
   ● Motor overload protection gain
   In order to effectively protect the motor under different loads, it is necessary to adjust the motor overload 
protection gain according to the current output overload capacity
   FE.01 is set, the motor overload protection is an inverse time curve.
FE.00
Motor overload 
protection selection
1
0~1
0: disabled
1: allow
FE.01
Motor overload 
protection gain
1.00
0.20 ~ 10.00
--
FE.02
Motor overload 
warning function
00
0~1
0: invalid
1: valid
F E.03
Motor overload 
warning level
80%
(20 ~ 200)%
--
function code
name
default value
Predetermined area
Parameter Description
Figure 8-9-1 Schematic diagram of motor overload inverse time curve
Current
Motor overload
protection factor
10 min
Time t
   Overload protection gain FE.01 is set to 1.00 , the default inverse time characteristic of the motor overload 
protection is: the motor overload will be reported after 10 minutes of continuous operation at 150% of the rated
 current of the motor; the motor overload will be reported after 80 minutes of continuous operation at 110% of
 the rated current of the motor .
   ● Motor overload warning
   The motor overload warning function is used to output a warning signal to the control system through DO 
before the motor overload fault protection. The early warning coefficient is used to determine the degree of 
early warning before the motor overload protection, the larger the value, the smaller the early warning amount.
   When the accumulative output current of the inverter is greater than the product of the overload time (the
 accumulative value of the inverse time-limit curve of the motor overload protection) and the FE.03 motor 
overload pre-alarm level, the multi-function digital terminal DO of the inverter outputs a valid signal of the 
motor overload pre-alarm.
   In special cases, when the motor overload warning level FE.03 is set to 100%, the early warning advance 
amount is 0, and at this time the pre-alarm and overload protection occur simultaneously.
8.9.3 Phase loss protection
FE.24
Input phase loss detection 
selection
1
0~2
function code
name
default value
Predetermined area
Parameter Description
0: output phase loss software 
    does not detect
1: Output phase loss software 
    detection
FE.25
Output phase loss 
detection selection
1
0~2
0: Input phase loss hardware 
    detection
1: Input phase loss software 
    detection
2: Input phase loss software and 
    hardware are not detected
054
NVF2G-S Series Inverter User's Guide