NVF5 Series User Manual Appendix B Parameter list
Code
Name
Setting Range
Default
Change
F0.09 Minimum Frequency
0.00Hz F0.08
0.00 Hz
F0.10
Basic Operating
Frequency
0.00Hz F0.07
50.00 Hz
F0.11 Max. Output Voltage
0 480V
Depend on
Series
F0.12
Integral Keypad
(UP/DN)Regulation
Rate
0.01 99.99Hz/s
1.00 Hz/s
F0.13
(UP/DN
) Regulation
Control
Ones Place
After Speed
Setting by Integral
Keypad(UP/DN)
0Frequency Setting non
Storage When Power Off
1
Frequency Setting
Storage When Power Off
Tens Place
After Speed
Setting by Integral
Keypad(UP/DN)
0
Frequency Miantain
When Stop
1
Frequency Restor to
Initial When Stop
Hundreds PlaceAfter Speed
Setting by Digital
Terminals(UP/DN)
0Frequency Setting non
Storage When Power Off
1
Frequency Setting
Storage When Power Off
Thousands PlaceAfter Speed
Setting by Digital
Terminals(UP/DN)
0
Frequency Miantain
When Stop
1
Frequency Restor to
Initial When Stop
0x0000
F0.14 Accelerate Time 1
0.0 6500.0s
Depend on
Series
F0.15 Decelerate Time 1
0.0 6500.0s
Depend on
Series
F0.16 Carrier Frequency
0.5 16.0kHz
Depend on
Series
F0.17
PWM Frequency
Adjust Automatically
0No
1Yes
1
F0.18 Reserve
0 3
0
F0.19
Automatic Voltage
Regulating
0No Effect
1Always Effective
2