ARControl BMS Quick Start Guide
This quick start guide provides informaon regarding hardware installaon and using the the ARControl BMS Module. The
ARControl BMS should be installed according to the direcons provided in this guide and always be in compliance with local
electrical codes and the specicaons of the operang company. The full manual is available at www.arcontrolbms.com.
Proper Use of the BMS Module 1870-511
The valve output on the BMS Module is the system’s ESD valve and is intended to be installed upstream of all other valves in the
ARControl BMS installaon. The dual-probe thermocouple input on the BMS Module is intended to be used as the source for the
high-temperature cuto. If the BMS Module 1870-511 is used in a manner not specied by Cimarron Energy, Inc., the protecon
provided by the equipment may be impaired.
ARControl Installaon Guidelines
• A switch or circuit breaker must be included in the installaon; it must be suitably located and easily reached. It
must be marked as the disconnecng device for the equipment.
• Proper earth grounding per local electrical codes must be ulized in the installaon.
• If the ARControl is used in a manner not specied by Cimarron Energy, Inc., the protecon provided by the
equipment may be impaired.
• If the BMS Module (1870-511) is used in conjuncon with the ARControl it must be mounted externally of the
ARControl in order for the ARControl to remain regulatory compliant.
• Use the hardware supplied with the ARControl. The hardware kit supplied with the ARControl contains an
aluminum pre-drilled mounng bracket, and (4) 3/4-inch bolts and nuts.
• Locate the unit out of trac and working areas, away from excessive heat, and above areas where water and
liquids may accumulate. Visibility of the display will be enhanced if not facing direct sun.
• Measure the wiring distance. The ignion cable is restricted to a length of 25 feet maximum.
ARControl BMS Installaon
Follow these steps to install the ARControl BMS (opons for DIN mount or CID1, temperature or pressure control):
WARNING: Do not apply power to the system unl instructed to do so in step 16. Failure to comply may result in serious
personal injury or death.
1. Locate and open the hardware kit.
2. Aach the mounng anges to the back of the ARControl (1960-155) with the supplied hardware.
3. Drill holes in the boom of the enclosure to accommodate the cables and conduit to the unit. It is recommended to use a
step drill bit to drill the holes.
4. Mount the ARControl via the anges to a secure locaon and away from heat sources.
5. Mount provided ignion rod assembly to the pilot or burner assembly.
6. When installing the BMS Module with included DIN bracket (1960-171) inside of the ARControl:
a. Aach provided cable conduit using provided glands to enclosure and burner chamber.
b. Mount the ignion module to the DIN rail on the inside of the enclosure. WARNING: Mounng ignion module inside
enclosure VOIDS the 1960-155 ARControl Class I Division 2 rang.
c. Wire the ignion module to the ARControl’s MODULE PORT using the provided wiring harness.
7. When installing the BMS Module with Class 1 Division 1 enclosure (1960-170) external from the ARControl:
a. Mount the BMS Module enclosure near the burner of the process equipment.
b. Aach suitable cable conduit between the ARControl and BMS Module.
c. Aach suitable cable conduit between the BMS Module and burner chamber.
d. Wire the ignion module to the ARControl’s MODULE PORT using suitable 4-conductor cable (Image 1.1.1).
8. Connect the ignion wire to the tab of the BMS Module spark transformer, run it through the conduit and aach it to the
ignion rod assembly.
9. Aach the free end of the grounding wire (green wire with yellow trace) to the burner’s chassis.
10. Install dual-probe thermocouple (148197) in process equipment or combustor stack.
11. Wire dual-probe thermocouple to the BMS Module’s thermocouple ports using k-type thermocouple extension wire.
12. If using Pressure Control (old SAU funconality), install 0-5 psig transducer (8100-020) in the process gas stream
and wire the transducer to the ARControl Transducer Port (Image 1.1.1).
13. Install the ESD valve upstream of the pilot and process valves and wire the ESD valve to the VALVE output of the
BMS Module.
14. Install the pilot valve upstream of the pilot and wire the pilot valve to the Pilot Valve output of the ARControl.