4-10
Cisco 6160 Hardware Installation Guide
OL-2190-02 B0
Chapter 4 Installing a Cisco 6160 Without a POTS Splitter Configuration
Installation Procedures
Step 5 Use a flat-head screwdriver and a counterclockwise motion to open the grounding terminal connector on
the power terminal block. This step ensures that the correct opening is presented for the wires. (See
Figure 4-5.)
Figure 4-5 Positioning the Power and Ground Terminals to Accept Wires
Step 6 Insert one end of the grounding wire into the grounding receptacle, which is the bottom receptacle in the
power terminal block connector (Callout 3 in Figure 4-6). The stripped part of the wire must be fully
inserted into the terminal block so that no bare wire is exposed.
Figure 4-6 Inserting the Grounding and Power Wires into the Power Terminal Block Connector
Step 7 Verify that no wire strands are left outside the connector.
38345
Correct terminal
position (open)
Incorrect terminal
position (closed)
1 Power lead wire connection 3 Grounding wire connection
2 Battery return wire connection
PEM 1
-48/-60V
35A , 1280VA
69266
1
2
3