4-12
Cisco SCE8000 10GBE Installation and Configuration Guide
OL-21054-04
Chapter 4 Installing the Cisco SCE8000 Chassis
DC-Powered Systems
Table 4-5 lists the Cisco SCE 8000 DC power specifications.
Note The DC supplies each have the provision for a dual connection to the power source in order to permit
high-power operation without exceeding current ratings. For the Cisco SCE8000, it is not necessary to
connect both of these inputs to DC power sources; it is sufficient to connect only the '1' connections.
Table 4-5 Cisco SCE 8000 DC Power Supply Specification
Specification Acceptable Range
PWR-2700-DC/4 minimum
capability
1350 W output (1750 W input)
DC-input power consumption
• Single SCE8000-SCM-E module:
1000 W (21 A @ 48 VDC, 17 A @ 60 VDC)
• Dual SCE8000-SCM-E modules:
1430 W (30 A @ 48 VDC, 24 A @ 60 VDC)
DC-input voltage rating -48 VDC to -40 VDC
(operating range: -40.5 VDC to -72 VDC)
DC-input current rating 45 A maximum at 120 VAC
DC-input cable Accepts 2-14 AWG copper conductors. Actual size of the wire
needed is determined by the installer or local electrician.
Terminal block material rated at 150°C (302°F).
DC-input circuit breaker For multiple DC input power supplies, each DC input must be
protected by a dedicated two-pole circuit breaker or a fuse.
The circuit breaker or the fuse must be sized according to the power
supply input power rating and any local or national electrical code
requirements.