M42740M4-02 02/10/08 page 23
LIST OF THE PARAMETERS ACCESSIBLE BY THE THERMOSTAT
Par Description range UM Def.
P01 BandaLavoro: Working band
0 ÷ 15.0
°C 2.0
P02
MaxH2Ocool:
Water max. temperature for cooling operating
0 ÷ 30.0
°C 20.0
P03
MinH2OHeat:
Water min. temperature for heating operating
0 ÷ 40.0
°C 30.0
P05
TimeOnPeriodical
Defines the duration of the ON phase of the periodical
0 ÷ 999
min 2
P06
TimeOffPeriodical
Defines the duration of the OFF phase of the periodical
0 ÷ 999
min 5
P10
OffsetEco
0 ÷ 4.0
°C 3.0
P11 SetUrHeat: Heat UR set point
30 ÷ 70
% 50
P12 BandUrHeat: Intervention band of the heat humidifier
0 ÷ 10
% 5
P21
FanOffCool:
Fan status at “cooling” thermoregulator, satisfied.
0: stop, 1: continuous , 2: periodical
0…2 num 2
P22
FanOffHeat:
Fan status at “heating” thermoregulator, satisfied.
0: stop, 1: continuous , 2: periodical
0…2 num 0
P31
ModoAuto:
It enables the automatic saison change
0: Manual, 1: Auto
0…1 flag 0
P41 BT1 probe calibration
-9.9 +10.0 °C 0.0
P42 BT2 probe calibration
-9.9 +10.0 °C 0.0
P43 Thermostat temp. probe calibration
-9.9 +10.0 °C 0.0
P44 Thermostat UR probe calibration
-9.9 +10.0 %UR 0.0
S01 TESToperativa
°C
S02 TH2Ooperativa
°C
S03 TARIAoperativa
°C
S04 URoperativa
Hr%
S05 Actual mode
bitmap
S06 CurrentSetpoint
°C
S07 Current humidity Set
Hr%
S08 Errors
bitmap
S09 Active humidifcation
flag
S10 Active dehumidification
flag
S11 FanStatus : 0: off, 1: on
0…1 flag
S12
Actual fan:
0-7 if motor 0-10 V
0-3 if 3 speed motor
0-1 if single-speed motor
0…7 num