80
M0CZ00007-03
Manufacturer parameters
Id 39 MaxSetHeat
Max Set in heat
Min -60 Max 90
Value 40.0
SYSTEM COMPONENT ADDRESSING
Enter the Maintenance operator password to access the
parameters.
Min - 60.0
Max 90.0
50
Press.
Rotate to select the "Scheduling" menu.
Press.
Rotate to select the "Configuration" menu.
Press.
Rotate to select the "Machine" menu.
Press.
Rotate to select the unit.
Press.
Select the parameter to be modified.
Press
Enter the value.
Press
Press to return to the main screen.
Main Menu
Stata
Alarms
Configuration
Date and hour
Configuration Menu
Keypad
Unit
System’s variables
Unit configuration
All
Configuration
Setpoint
Charge compensation
Manufacturer parameters
Id 39 MaxSetHeat
Max Set in heat
Min -60 Max 90
Value 40.0
Main Menu
Stata
Scheduling
Date and hour
Password
Manufacturer parameters
Id 39 MaxSetHeat
Max Set in heat
Min -60 Max 90
Value 50.0
VULCAN MEDIUM
Vulcan Medium - Parameters to be modified
Parameter
Mnemonic
Name
Description Value
315 Address ModBus supervision serial address 2
316 Baud Rate Baud Rate (0=4800 / 1=9600 2 =19200) 1
317 Parity
Parity 0=NO / 1=Odd 2=Even supervision
serial
0