SYSTEM COMPONENT CONFIGURATION
Remote On / off from telephone dial
Par.49 Configuration
CLOSE
OPEN
Note
0 Not used
1
System
(NC)
System OFF
DHW OFF
System ON-OFF from CONTROL4 NRG
keypad disabled
System ON
DHW ON
System ON-OFF from CONTROL4 NRG key-
pad
At CLOSED contact it switches
off the whole system including
DHW
2
Air-conditioning only
(NC)
System OFF
DHW ON
(ONLY DHW)
System ON-OFF from CONTROL4 NRG
keypad
System ON
DHW ON
(NORMAL CONF. )
System ON-OFF from CONTROL4 NRG key-
pad
At CLOSED contact is switches
off only the air-conditioning
system, leaving the DHW pro-
duction active.
3 System (NA)
System ON
DHW ON
System ON-OFF from CONTROL4 NRG
keypad
System OFF
DHW OFF
System ON-OFF from CONTROL4 NRG
keypad disabled
At OPEN contact it switches off
the whole system including DHW
4
Air-conditioning only
(NA)
System ON
DHW ON
(NORMAL CONF. )
System ON-OFF from CONTROL4 NRG
keypad
System OFF
DHW ON
(ONLY DHW)
System ON-OFF from CONTROL4 NRG key-
pad
At OPEN contact is switches off
only the air-conditioning system,
leaving the DHW production
active.
Configure parameter 49. Use remote consent in the Advanced settings
GENERIC INPUT/OUTPUT MODES PROVIDED BY THE MULTIPLE RADIANT AREA MODULE