EasyManuals Logo

CLIVET CRC 242 User Manual

CLIVET CRC 242
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
page 23
TECHNICAL DATA
UNIT
Product
-
CRC
Size
-
242
Direct expansion refrigeration circuit
-
cooling only unit
Refrigerant circuit
-
air-air
Refrigerant
-
R-134a
Equipping
Constructive version
-
CB (fresh air chamber on-off)
Air filter
-
G4
free-cooling thermal ON-OFF
FC
standard
Constructional characteristics
Installation
-
outside
Thick sandwich panels air handling section
mm
40
Air Handling Section Fans
Outlet air flow-rate
m
3
/h (l/s)
7.000
1.944
Static pressure outlet + inlet (max value, excluded accessories)
Pa
350
Fresh air flow-rate
m
3
/h (l/s)
0÷7000
0÷1944
Intake air flow
m
3
/h (l/s)
7000÷0
1944÷0
Cooling
Indoor reference conditions
°C / %
35
20
Outdoor reference conditions
°C / %
55
20
Sensible cooling capacity
kW
40,9
Compressor power input
kW
18,7
COMPRESSOR
Type of compressors / No. of Compressors / Std Capacity control steps
no.
Scroll / 2 / 2
Refrigerant circuits
no.
2
EXTERNAL SECTION FANS
Type of fans / Number of fans
axial-flow
2
Fan diameter / Fan RPM
mm/rpm
800
880
Standard air flow
m
3
/h (L/s)
30.000
8.333
ELECTRICAL DATA
Power supply
V
400/3/50-460/3/60
FLI total
kW
35,9
FLA total
A
57,2
Dimensions
Length
mm
1.980
Width
mm
1.250
Height
mm
2.160
Note:
Max operating temperature 55°C
Max storage temperature 70°C