EasyManua.ls Logo

CLIVET MC2-Y 160T - Page 63

CLIVET MC2-Y 160T
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
Page 63
Model
ID2-XY 160M
Pipe Length (m)
MC2-Y 160T
Cooling 5 15 25 35 50 65
Height
difference
H (m)
Indoor Upper
than Outdoor
30 0.866 0.816 0.767
20 0.908 0.875 0.825 0.774
10 0.951 0.917 0.884 0.833 0.782
5 0.995 0.961 0.927 0.893 0.841 0.790
0 1.000 0.966 0.931 0.897 0.846 0.794
Outdoor Upper
than Indoor
-5 1.000 0.966 0.931 0.897 0.846 0.794
-10 0.966 0.931 0.897 0.846 0.794
-20 0.931 0.897 0.846 0.794
-30 0.897 0.846 0.794
Heating 5 15 25 35 50 65
Height
difference
H (m)
Indoor Upper
than Outdoor
30 0.953 0.929 0.905
20 0.968 0.953 0.929 0.905
10 0.984 0.968 0.953 0.929 0.905
5 1.000 0.984 0.968 0.953 0.929 0.905
0 1.000 0.984 0.968 0.953 0.929 0.905
Outdoor Upper
than Indoor
-5 0.992 0.976 0.961 0.945 0.921 0.898
-10 0.968 0.953 0.937 0.914 0.891
-20 0.945 0.930 0.907 0.883
-30 0.922 0.899 0.876

Other manuals for CLIVET MC2-Y 160T

Related product manuals